If the foundation is not firm enough, it may warp
and cause some space between its center and
the showcase bottom. In this case, provide a
support to keep the foundation level.
No good
Fig. 3
* Avoid a site where dripping is not allowed.
* Do not expose the showcase to direct sunlight
or higher temperatures to prevent damage to the
plastic housing.
* Allow at least 15 cm clearance between the
Condenser air outlet and the wall or other
equipment for proper air circulation. The rear and
top of the showcase should have enough space
(at least 100 cm) for proper air circulation and
smooth operation.
Air Outlet
100cm
Fig. 4
3. SET UP
IMPORTANT
Carry the showcase by holding its bottom.
1) Unpack the showcase, and remove all shipping
carton, evaporator spacer, tapes and packing
BEFORE operating the unit. Be careful not to
damage the exterior panels when handling the
showcase.
2) Position the showcase in a selected site. Clean
the interior with soap and water and rinse
thoroughly.
Good
Support
Air Inlet
100cm
Unit Height
15cm
3) Level the showcase in both the left-to-right and
the front-to-rear directions.
4) The perimeter where the machine touches the
counter should be sealed with silicone.

4. ELECTRICAL CONNECTIONS

* T h i s s h o w c a s e m u s t b e p l u g g e d i n t o t h e
separated power receptacle which has enough
capacity. The maximum allowable voltage
variation should not exceed ± 6 percent of the
nameplate rating. See the nameplate.
* If the supply cord and the plug should need to be
replaced, it should only be done by a qualified
service engineer in order to avoid a hazard.

5. DRAIN CONNECTIONS

* The hose may be connected to either right or left
joint, whichever is convenient.
* The joint must be tilted as shown below to turn
the hose connection downward.
* Keep more than 5 cm air gap between the
vertical drain pipe end and the sink.
No good
Joint
Hose
Joint

6. FINAL CHECK LIST

1) Is the showcase level?
2) Is the showcase in a site where the ambient
temperature is within 10°C to 30°C all year
around?
2
Good
Joint
Hose
Hose
Joint
To floor drain
or sink
Fig. 5