SMART AUTOMATION BY-ME PLUS
01456
Actuator with relay output 16 A 120-230 V~ 50/60 Hz with integrated current sensor, 1 input channel for toroidal residual current sensor, DIN rail installation
(60715 TH35), occupies 1 17.5 mm module. Supplied without toroidal residual current sensor (art. 01459).
The device performs the function of an actuator and measures the power and calculates
the consumption; it also records the power values and enables alarm signalling due to
malfunctioning such as current leakage and load faults. The device can be used in auto-
mation, energy saving and HVAC management systems.
CHARACTERISTICS.
• Rated supply voltage mains: 120-230 V~, 50/60 Hz
• Rated supply voltage TP Busbar: 29 V
• Absorption from TP Busbar: 5 mA
• Terminals:
- TP bus
- 1, L, N, N
• Operating temperature: +5 °C - +40 °C (indoor)
• 1 module of 17.5 mm
• IP20 protection rating
• Overvoltage category: III
• Measurement category: III
OPERATION.
• Measuring the power absorbed by the load.
• Monostable/bistable relay behaviour.
• Delay in activation, deactivation and duration.
• Load fault alarm with fault detection power threshold.
• Current leakage alarm with settable current threshold.
• Settable automatic switch-off in case of a leakage alarm.
• Scenario control.
• Power value recording.
CONTROLLABLE LOADS.
• The controllable loads at 120 - 230 V ~ (NO contact) are:
- resistive loads: 16 A (20,000 cycles)
- incandescent lamps: 8 A (20,000 cycles)
- fluorescent lamps and energy saving lamps: 1 A (20,000 cycles)
- electronic transformers: 4 A (20,000 cycles)
- ferromagnetic transformers: 10 A (20,000 cycles)
- cos ø 0.6 motors: 3.5 A (100,000 cycles)
MANUAL MANAGEMENT.
When the actuator is not configured, pressing the CONF button performs the switching
of the relay.
CONFIGURATION.
FOR THE OPERATIONS OF CONFIGURATION, SEE THE INSTRUCTIONS MANUAL
FOR THE By-me Plus SYSTEM.
• Functional blocks: 2 (1 actuator, 1 meter), each actuator functional block can belong to
at most 4 groups.
• Selection of the functional unit in the configuration phase:
- Press the configuration button to identify the desired functional unit: pressing it once
identifies the actuator's functional unit (configuration LED blinks slowly) while pressing
it a second time identifies the meter's functional unit (configuration LED blinks fast).
On pressing again it restarts from the actuator functional unit.
- Wait approximately 3 s for the enrolment procedure to start.
- The configuration starts when the red LED comes on steady and ends when it goes out.
With the device not configured, the actuator functions are inhibited.
INSTALLATION RULES.
Installation should be carried out by qualified staff in compliance with the current regula-
tions regarding the installation of electrical equipment in the country where the products
are installed.
• Before working on the system, cut off power with the main switch (
• Important: The two neutral terminals are connected to each other. Do not use the
neutral terminals as outputs to power the load.
• This device is compliant with the reference standard, in terms of electrical safety, when
it is installed in the relevant consumer unit.
• If this device is used for purposes not specified by the manufacturer, the protection
provided may be jeopardized.
• Observe the maximum current and voltage values given for the device.
• The network power supply circuit must be protected against overload by a device, fuse
or circuit breaker with a rated current not exceeding 16 A.
REGULATORY COMPLIANCE.
LV directive. Standards EN 61010-1, EN 61010-2-030.
EMC directive. Standards EN 61000-6-1, EN 61000-6-3.
REACH (EU) Regulation no. 1907/2006 – Art.33. The product may contain traces of lead.
49400548A0 05 2201
FRONT/SIDE VIEW AND TERMINALS
Input for
current
sensor
Configuration
button and
the manual
activation
of the actuator
CONNECTIONS
L
N
Bus
symbol).
WEEE - Information for users
If the crossed-out bin symbol appears on the equipment or packaging, this means the product must not be included
with other general waste at the end of its working life. The user must take the worn product to a sorted waste center, or
return it to the retailer when purchasing a new one. Products for disposal can be consigned free of charge (without any
new purchase obligation) to retailers with a sales area of at least 400 m
sorted waste collection for the environmentally friendly disposal of the used device, or its subsequent recycling, helps
avoid the potential negative effects on the environment and people's health, and encourages the re-use and/or recycling
of the construction materials.
1 L
N N
TP BUS terminals
LOAD
01459 (optional)
The current sensor can be
installed in any position
OPTIONAL CURRENT
SENSOR (Art. 01459)
Toroidal residual
current sensor
Input cable at the
terminals of the actuator
2
, if they measure less than 25 cm. An efficient
Viale Vicenza, 14
36063 Marostica VI - Italy
www.vimar.com