Group control through a remote control
If U series models (TU2C-Link) are combined with models other than U series (TCC-Link),
the wiring specifications and maximum number of connectable indoor units will be changed.
Group control of multiple indoor units (16 units) through a single remote control switch
Indoor unit
N
o
1 .
N
o
2 .
A
B
A
B
(A.B)
Remote control
Max. number of connectable indoor units, and communication type
O
u
d t
o
r o
u
n
t i
U
s
r e
e i
s
n I
d
o
r o
u
n
t i
U
s
r e
e i
s
Remote control
U
s
r e
e i
s
TU2C-
Communication type
Link
Max. number of connectable
1
6
units
: Other than U series
Power supply wire connection
1. Insert the power supply wires from lower right of the electrical control box and connect them to the power
terminal blocks and the grounding line to the grounding screw, and then fix each of the five wires with each
cord clamp and binding band.
2. When finished wiring the power supply wires, get each of five wires through the cutout on the sealing material
(black) under the cord clamp to pull it outside the electrical control box. Tear upper and lower of the cutout on
the sealing material with your hands before getting the wires through the cutout.
3. Get the binding band through two holes in the right part of the valve fixing plate and fix the power supply wires
with it.
1" (25 mm)
or more
Tear upper and lower of the
sealing material.
Grounding line
45-EN
N
o
3 .
N
o
4 .
N
. o
15
A
B
A
B
A
B
Unit type
U
s
r e
e i
s
U
s
r e
e i
s
U
s
r e
e i
s
U
s
r e
e i
s
U series
U series
U series
U series
TCC-Link
8
Clamp base
Sealing material
Get the binding band through the hole at
one side of the clamp base and fix the
power supply wire securely with it.
Power supply wire
– 23 –
Connection of power supply wires and communication wires
Remove knockouts on the piping / wiring panel on the front of the unit and the panel on the bottom to get the
power and communication wires through the holes.
1. Connect the power supply conduit to the field wiring panel.
2. Route the power supply wiring through the raceway and connect to the power supply terminal block and
ground screw.
3. Use ring terminals on field power wires if required by NEC and local codes.
N
. o
16
A
B
Power supply terminal block
Grounding screw
Power supply
wires
U series
Wire clamp
NOTE
Be sure to separate the power supply wire and communication wires.
Bundle the control wires in the cutout so that they do not get caught in the electrical control box cover.
Communication terminal block
Communication
wires
Wire clamp
Piping/wring panel
Conduit
Knockout for
communication wires
Knockout for power supply wires
(When using wire size
A
AWG 14, AWG 12 or AWG 10.)
B
Knockout for power supply wires
(When using wire size
AWG 8, AWG 6 or AWG 4.)
46-EN