Name
(b)
/5
Unit of measure:
▪ 0: °C
▪ 1: °F
/6
Display decimal point:
▪ 0: Yes
▪ 1: No
/t1
Display on user terminal:
▪ 0: not configured
▪ 1: value of S1
▪ 2: value of S2
▪ 3: value of S3
▪ 4: value of S4
▪ 5: value of S1H
▪ 6 to 8: not available
▪ 9: control probe
▪ 10: virtual probe
▪ 11 to 14: not available
▪ 15: current control setpoint
/t2
Display on remote display:
▪ 0 to 15, see /t1 (above)
(b)
A1
Alarm thresholds (AH, AL) relative to the setpoint St or
absolute:
▪ 0: relative
▪ 1: absolute
(b)
A3
Defrost terminated after maximum time signal:
▪ 0: disabled
▪ 1: enabled
(b)
Ad
Delay time for high and low temp. alarms (AH, AL)
(b)
Add
High temp. alarm bypass time for door open
(b)
AH
Relative high temperature alarm threshold
(b)
AL
Relative low temperature alarm threshold
(b)
Alr
Alarm present
(b)
d2
Network end defrost synchronised for Primary unit controller
(c)
d6
Display on terminals during defrosts:
▪ 0: temperature alternating with "PSd"
▪ 1: freeze display
▪ 2: "PSd"
d8
Bypass time high temperature alarm after defrost
(b)
dAs
DAY status/ECO mode
(b)
dC
Time base for defrosts:
▪ 0: dI in hours, dP1, and dP2 in minutes
▪ 1: dI in minutes, dP1 and dP2 in seconds
(b)
dC1
Time base for d8:
▪ 0: d8 in minutes
▪ 1: d8 in seconds
LMSEY1A09/13 + LMSEY2A19/25
Daikin LMS
4P728170-1B – 2023.07
Description
Default
Min.
Max.
0
0
1
0
0
1
9
0
15
0
0
15
0
0
1
0
0
1
120
0
240
5
1
240
0
0
555/
∆°C/°F
999
0
0
200/
∆°C/°F
360
0
0
1
0
0
1
1
0
2
1
1
240
1
0
1
0
0
1
0
0
1
6 Configuration
(a)
UoM
Menu
App
●
●
Pro
●
●
Pro
●
●
Pro
●
●
Pro
●
●
min
●
●
ALM
min
●
●
ALM
●
●
ALM
●
●
ALM
●
●
●
hours
●
●
●
●
Installation manual