NOTICE
ONLY applicable if the power supply is three‑phase, and
the compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a
momentary black out and the power goes ON and OFF
while the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed
phase can break the compressor and other parts.
2.3
Standards and regulations
Directives
Directive and
regulations
Harmonised standards EN 378-1:2016: Refrigerating systems and
heat pumps - Safety and environmental
requirements: Basic requirements,
definitions, classification and selection
criteria
EN 378-2:2016: Refrigerating systems and
heat pumps. Safety and environmental
requirements: Design, construction, testing,
marking and documentation
EN 60204-1:2018: Safety of machinery -
Electrical equipment of machines - Part 1,
General requirements
IEC 60335-2-89: Household and similar
electrical appliances - Safety - Part 2-89,
Particular requirements for commercial
refrigerating appliances and ice-makers
with an incorporated or remote refrigerant
unit or motor-compressor.
EN 12100 Risk assessment
EN ISO 13857 :2020 Safety Distances
EN ISO 13854:2020 Minimum gaps
RED
Harmonised standards IEC 61000-6-8: Emission
IEC 61000-6-2: Immunity for Industrial
EN IEC 61000-3-2: ElectroMagnetic
Compatibility (EMC) Part 3-2, Limits - Limits
for harmonic current emissions (equipment
input current <= 16 A per phase)
EN IEC 61000-3-3: ElectroMagnetic
Compatibility (EMC) - Part 3: Limits -
Section 3, Limitation of voltage fluctuations
and flicker in low-voltage supply systems
for equipment with rated current ≤ 16 A
EN 301 489-1: ElectroMagnetic
Compatibility (EMC) standard for radio
equipment and services; Part 1, Common
technical requirements; Harmonised
Standard for ElectroMagnetic Compatibility
EN 301 489-17, ElectroMagnetic
Compatibility (EMC) standard for radio
equipment and services; Part 17, Specific
conditions for Broadband Data
Transmission Systems; Harmonised
Standard for ElectroMagnetic Compatibility
ETSI EN 300 328, Wideband transmission
systems; Data transmission equipment
operating in the 2,4 GHz band; Harmonised
Standard for access to radio spectrum
RoHS
Harmonised standards
LMSEY1A09/13 + LMSEY2A19/25
Daikin LMS
4P728170-1B – 2023.07
2006/42/CE
EMC 2014/30/EU
RoHS 2011/65/EU
IEC EN 63000
Performance
EN 17432:2021 Packaged refrigerating units for walk-in cold rooms
- Classification, performance and energy consumption testing
Regulations
Regulation (EC) No
Registration, Evaluation, Authorisation and
1907/2006
Restriction of Chemicals (REACH)
3
About the box
▪ At delivery, the unit MUST be checked for damage and
completeness. Any damage or missing parts MUST be reported
immediately to the claims agent of the carrier.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
▪ Prepare in advance the path along which you want to bring the
unit to its final installation position.
▪ When handling the unit, take into account the following:
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor
damage.
▪ A forklift can be used for transport as long as the unit remains on
its pallet.
3.1
To unpack the unit
The packaging consists of a wooden pallet (d) on which the unit is
fixed in the upright position. The unit is supported with two cardboard
pillars (b) keep the evaporator (a) upright.
The cardboard protection (e) protects the unit and is secured by
straps (c).
a
a
Evaporator
b
Cardboard pillars
c
Straps
d
Pallet
e
Condenser cardboard protection
The pallet and unit are protected by a cardboard box (e). Parts of the
pallet are intentionally covered to obtain optimal load balance when
using a forklift (f).
3 About the box
b
c
d
e
Installation manual
5