248 Technical data and references
Frame
ACS580-04...
size
880A-4
R11
1) Typical drive losses when it operates at 90% of the motor nominal frequency and 100% of the motor nominal
current.
Typical power cable sizes
The table below gives copper and aluminium cable types with concentric copper shield
for the drives with nominal current. See also section
power cables (page
ACS580-04-...
U
= 400 V
n
505A-4
585A-4
650A-4
725A-4
820A-4
880A-4
U
= 480 V
n
505A-4
585A-4
650A-4
725A-4
820A-4
880A-4
1) The cable selection is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top
of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F) (EN 60204-1 and
IEC 60364-5-52). For other conditions, select the cables according to local safety regulations, appropriate input
voltage and the load current of the drive.
Air flow
3
m
/h
1420
249).
Cu cable
2
mm
3 × (3×95)
3 × (3×120)
3 × (3×150)
3 × (3×185)
3 × (3×240)
3 × (3×240)
3 × (3×95)
3 × (3×95)
3 × (3×120)
3 × (3×150)
3 × (3×185)
3 × (3×240)
Typical power
cfm
848
Terminal and entry data for the
1)
IEC
Al cable
mm
3 × (3×150)
3 × (3×185)
3 × (3×240)
4 × (3×185)
4 × (3×240)
4 × (3×240)
3 × (3×150)
3 × (3×150)
3 × (3×185)
3 × (3×240)
4 × (3×185)
4 × (3×240)
Noise
1)
loss
W
dB(A)
10887
71
2