The dryer doesn't drain the condensate
The dryer continuously drains condensate.
Water within the line.
If installed - HPS high pressure switch has
been activated.
If installed - LPS low pressure switch has been activated.
If installed - TS safety thermo switch has been activated.
Electronic instrument DMC15
The first and the last led of display are
flashing syncronous.
Electronic instrument DMC15
The
yellow led is flashing
Electronic instrument DMC15
The first led of the display is flashin
Electronic instrument DMC15
The last led of the display is flashing
NOTE: When the drain is in alarm condition, the diaphragm solenoid valve will open 7.5 sec every 4 min.
The condensate drain service valve is closed - open it.
Condensate strainer is clogged – remove and clean it.
The drain solenoid valve is jammed – remove and clean it.
Verify the electric wiring.
The coil of the drain solenoid valve is failed – replace it.
Electronic instrument is faulty – repace it.
The DewPoint is too low - the condensate is frost and blocks the air - see specific point.
Inlet compressed air pressure is too low and condensate is not drained – restore nominal conditions.
Electronic drainer is not operating correctly (see paragraph 9.13).
The drain solenoid valve is jammed – remove and clean it.
Try to remove the electric connector on the solenoid valve - if drain stops verify the electric wiring or the
electronic instrument is faulty - replace it
Electronic drainer is dirty (see paragraph 9.13).
The dryer doesn't start - see specific point.
If installed - Untreated air flows through the by-pass unit - close the by-pass.
The dryer doesn't drain the condensate - see specific point.
DewPoint too high - see specific point.
Check which of the following has caused the activation :
1. The ambient temperature is too high or the room aeration is insufficient - provide proper ventilation.
2. The condenser is dirty - clean it.
3. The condenser fan doesn't work - see specific point.
Reset the pressure switch pressing the button on the controller itself - verify the dryer for correct operation.
HPS pressure switch is faulty - contact a refrigeration engineer to replace it.
There is a leak in the refrigerating fluid circuit - contact a refrigeration engineer.
The pressure switch reset automatically when normal conditions are restored - check the proper operation
of the dryer.
Check which of the following has caused the activation :
1. Eccessive thermal load – restore the standard operating conditions.
2. The inlet air is too hot - restore the nominal conditions.
3. The ambient temperature is too high or the room aeration is insufficient - provide proper ventilation.
4. The condenser unit is dirty - clean it.
5. The fan doesn't work - see specific point.
6. The hot gas by-pass valve requires re-adjusting – contact a specialized technician to restore nominal
setting.
7. Refrigerant gas leak - contact a refrigeration engineer.
Reset the thermo switch by pressing the button on the thermo switch itself – verify the correct operation
of the dryer.
TS thermo switch is faulty - replace it.
Verify the electric wiring of T1 DewPoint probe.
The T1 DewPoint probe is faulty - replace it.
The electronic instrument is faulty - replace it.
ADS 10-100 - Verify the electric wiring of T2 fan control probe.
ADS 10-100 - The T2 fan control probe is faulty - replace it.
ADS 125-480 - Verify the electric wiring of resistance on terminal 1 and 2
The electronic instrument is faulty - replace it.
DewPoint too low - see specific point.
The T1 DewPoint probe is faulty - replace it.
The electronic instrument is faulty - replace it.
DewPoint too high - see specific point.
The T1 DewPoint probe is faulty - replace it.
The electronic instrument is faulty - replace it.