Error messages
The error numbers are not displayed for units with standard controllers: With the ECoolPLANT software error
numbers can be read on the computer.
The blinking of the red LED light on the controller circuit board is not a fault indicator or error message. The red
LED light indicates that voltage is supplied to the cooling unit.
Error
Fault
no.
Er00
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
Er01
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
Fault signal contact:
Er04
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
Fault signal contact:
Er05
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• External heating:
Fault signal contact:
Operating Manual DTS and DTI 6201C / 6301C Multi-Controller (MC) 086100014c © Pfannenberg GmbH
Unit activity
Possible causes
• Door contact:
Blinking
• The door contact loop has
OFF
been interrupted.
OFF
OFF
OFF
Closed
• Pressostat tripped:
Blinking
• Excessively high pressure
OFF
has built up in the
ON
refrigerant circuit. The
cooling unit cannot
ON
dissipate the heat from the
OFF
refrigerant circuit.
Open
• Phase sequence / phase
Blinking
OFF
loss:
• Failure of at least one
OFF
phase or phase sequence
is incorrect (only with
OFF
alternating current units
OFF
with rotating piston
Open
compressors).
• Sensor 1 (TS1) defective. Replace Sensor 1 or the
Blinking
ON
ON
ON
OFF
Open
Corrective measures
Close door.
Connect door contact
switch.
Bypass door contact.
Check wiring.
Allow the unit to cool
down.
Clean the heat
exchanger fins
(internal/external).
Check condenser fan
(external) for function.
Check the field of
rotation - (clockwise
rotation is required).
All phases must carry
rated operational
voltage.
controller circuit board
according to the unit
type.
Replace controller circuit
board if the sensor is
soldered in place.