GB
Error messages
Error
Fault
no.
Er06
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
Er07
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
Er08
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
Operating Manual DTS and DTI 6201C / 6301C Multi-Controller (MC) 086100014c © Pfannenberg GmbH
Unit activity
Possible causes
• Sensor 1 Minimum:
Blinking
• Minimum switch cabinet
OFF
temperature value "Lit_"
ON
(LCD) is reached
or exceeded.
ON
OFF
Open
• Sensor 1 Maximum:
Blinking
• The maximum value of the
ON
switch cabinet
ON
temperature "Lit¯" (LCD)
has been reached or
ON
exceeded.
• The cooling unit cannot
OFF
Open
sufficiently cool the air in
the switch cabinet.
• Sensor 2 (TS2) defective. Replace Sensor 2 or the
Blinking
ON
ON
ON
OFF
Open
Corrective measures
Select higher switch
cabinet
temperature setpoint.
Inspect the switch
cabinet for leaks.
Move components near
the air inlet and outlet
further away in order to
prevent an air short
circuit. (Cold air is
diverted directly to the air
inlet by components.)
Check the settings of the
cooling unit.
Clean the heat
exchanger fins
(internal/external).
Check evaporator fan
(internally) for
functionality.
Check the refrigeration
circuit for escaping
refrigerant or leaks.
If necessary, install a
cooling unit with a higher
cooling capacity.
controller circuit board
according to the unit
type.
Sensor 2 is plugged into
the circuit board, not
permanently soldered in
place.
Page 32 / 43