Descargar Imprimir esta página

+GF+ SPC Manual De Instrucciones página 24

Publicidad

Idiomas disponibles

Idiomas disponibles

Type SPC positioner
5.2.1
DIP switch
NOTE!
To be able to operate the DIP switches and buttons, make sure that the local operation lock is deactivated/not locked (factory setting):
with communication software or fieldbus communication.
Positions of the DIP switches
ON
OFF
ON
OFF
5.2.2
Functions of the DIP switches
ON DIP
1 2 3 4
* Can be changed with communication software.
24
Function
ON
OFF
But-
Function
ton
1
ON
Reversal of the operating direction of the setpoint value (20 - 4 mA corresponds
to 0 - 100%), falling (DIR.CMD)
OFF
Normal operating direction of the setpoint value (4 - 20 mA corresponds to 0 -
100%), increasing
2
ON
Tight-closing function active. The valve closes below 2%* and opens completely
above 98%* of the setpoint value (CUTOFF)
OFF
No tight-closing function
3
ON
Correction characteristic for adjusting the operating characteristic (CHARACT)*
OFF
Linear characteristic
4
ON
Operating state Manual
OFF
Operating mode AUTOMATIC
Operating Instructions

Publicidad

loading