Descargar Imprimir esta página

Briggs & Stratton PowerBoss 3250 Watt Handyman-Plus Manual De Instrucciones página 8

Publicidad

Idiomas disponibles

Idiomas disponibles

Connecting Electrical Loads
• Let engine stabilize and warm up for a few minutes after
starting.
• Plug in and turn on the desired 120 Volt AC, single phase,
60 Hz electrical loads.
• DO NOT connect 240 Volt loads to the 120 Volt duplex
receptacles.
• DO NOT connect 3–phase loads to the generator.
• DO NOT connect 50 Hz loads to the generator.
• DO NOT OVERLOAD THE GENERATOR. See
"Don't Overload the Generator" on page 9.
Stopping the Engine
• Unplug all electrical loads from generator panel
receptacles. NEVER start or stop engine with electrical
devices plugged in and turned ON.
• Let engine run at no-load for several minutes to stabilize
the internal temperatures of engine and generator.
• Move rocker switch to "Off" position.
• Move the fuel valve to the "Off" position.
RECEPTACLES
120 Volt AC, 20 Amp, Duplex
Receptacles
Each pair of receptacles (Figure 8) is protected against
overload by a 20 Amp push–to–reset circuit breaker.
PowerBoss 3250 Watt Handyman-Plus Generator
Figure 8 — 120 Volt, 20 Amp Duplex Receptacle
Use each receptacle to operate 120 Volt AC, single–phase,
60 Hz electrical loads requiring up to 2400 watts (2.4 kW)
at 20 Amps of current. Use cord sets that are rated for
125 Volt AC loads at 20 Amps (or greater).
8
CAUTION!
Although each receptacle is rated for
120 Volts at 20 Amps (2400 watts or 2.4 kW), the
generator is rated for a total of 3,250 watts.
Powering loads that exceed the wattage capacity of
the generator can damage it or cause serious
injuries.The total of loads powered through these
receptacles should not exceed 20 Amps.

Publicidad

loading