1 Ph / 50 Hz / 230 V
-
No option
-
Connection direction (no specific direction)
5
Unit installation
5.1
Preparing the installation site
NOTICE
The unit must be installed ≥2.5 m from the floor.
INFORMATION
The sound pressure level is less than 70 dBA.
CAUTION
Appliance NOT accessible to the general public. Install it in
a secured area, protected from easy access.
This unit is suitable for installation in a commercial and
light industrial environment.
NOTICE
Where installation from below is NOT possible, such as
very high ceilings, access to the unit for installation and
service should be possible from the top of the ceiling.
Select an installation site where the following conditions are fulfilled
and that meets your customer approval.
▪ The space around the unit is adequate for maintenance and
servicing. The space around the unit allows sufficient air
circulation and air distribution. See space required for installation.
NOTICE
If the switch box (c) is facing the wall, leave a service
distance of at least 600 mm and provide at least 1500 mm
space from air inlet (b) and air outlet (a) for air circulation.
a
▪ Make sure the area is well ventilated. Do NOT block any
ventilation openings.
▪ Make sure the installation site withstands the weight and vibration
of the unit.
▪ Take care that in the event of a water leak, water cannot cause
any damage to the installation space and surroundings.
▪ Choose a location where the operation noise or the hot/cold air
discharged from the unit will not disturb anyone and the location is
selected according the applicable legislation.
▪ Drainage. Make sure condensation water can be evacuated
properly.
▪ In places with weak reception, keep distances of 3 m or more to
avoid electromagnetic disturbance of other equipment and use
conduit tubes for power and transmission lines.
FWF02~05D
Fan coil units
3P443944-9T – 2023.01
Description
10mm
600
*
c
a
b
▪ Fluorescent lights. When installing a wireless remote control
(user interface) in a room with fluorescent lights, mind the
following to avoid interference:
▪ Install the wireless remote control (user interface) as close as
possible to the indoor unit.
▪ Install the indoor unit as far as possible from the fluorescent
lights.
Do NOT install the unit in places often used as work place. In case
of construction works (e.g. grinding works) where a lot of dust is
created, the unit MUST be covered.
Do not install or operate the unit in rooms mentioned below.
▪ Places with mineral oil, or filled with oil vapour or spray, like in
kitchens (plastic parts may deteriorate).
▪ Where corrosive gas like sulphurous gas exists. Copper tubing
and brazed spots may corrode.
▪ Where the air contains high levels of salt, such as that near the
coast and where voltage fluctuates a lot (e.g. in factories). Also in
vehicles or vessels.
▪ In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system,
and cause malfunction of the equipment.
▪ In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre,
ignitable dust.
▪ The unit can NOT be installed in a bathroom.
5.2
Mounting the unit
5.2.1
To install the suspension bolts
Use the pattern to determine the suspension bolt positions (upper
part of the packing). Suspension bolt positions are indicated on the
paper pattern. Holes can be drilled by putting the paper pattern on
the ceiling.
a
Paper pattern for installation. (upper part of the packing)
▪ Ceiling strength. Check whether the ceiling is strong enough to
support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.
▪ For existing ceilings, use anchors.
▪ For new ceilings, use sunken inserts, sunken anchors or other
field supplied parts.
A
50~100 mm
a
Ceiling slab
b
Anchor
c
Long nut or turnbuckle
d
Suspension bolt
e
Suspended ceiling
5 Unit installation
a
a
b
c
d
e
Installation and operation manual