The Microprocessor Control provides a protected TECHNICIAN
MODE to manipulate several parameters not accessible by the
typical operator. This mode also permits viewing of the factory
settings to aid in troubleshooting of the dryer. Below is a list
of parameters that can be accessed and manipulated by the
technician in the TECHNICIAN MODE.
Parameter
DRAIN VALVE ENABLE DRAIN ENABLE
CRANKCASE HEATER
DELAY
AUTO RESTART
AUTO RESTART
ENABLE
In TECHNICIAN MODE, the following parameters can be viewed
but not changed:
Parameter
CONFIGURATION (# of
sensors)
OPERATING MODE
REFRIGERANT
CONDENSER TYPE
OPERATING TEMPERATURE
DIFFERENTIAL
SHORT CYCLE DELAY
HIGH PRESSURE CUTOUT
HIGH PRESSURE CUTOUT
DELAY
LOW PRESSURE CUTOUT
LOW PRESSURE CUTOUT
DELAY
HIGH TEMPERATURE ALARM HITEMP
LOW TEMPERATURE ALARM LOWTEMP
LOW TEMPERATURE ALARM
DELAY
FAN 1 ON PRESSURE
FAN 1 OFF PRESSURE
FAN 2 ON PRESSURE
FAN 2 OFF PRESSURE
ALARM LIST
10.1 ENTERING TECHNICIAN MODE
WARNING
TECHNICIAN MODE should only be entered by
qualified service personnel. Altering the set points in
TECHNICIAN MODE will have a significant effect on
the operation of the dryer. Incorrect set points may
damage dryer and cause potential serious injury.
10.0 TECHNICIAN MODE
Display
Set Point
ON (or OFF)
CCH DLY
8 (or 0,2,4,12
hours)
N (or Y)
Display
Set Point
CONFIG #:
1, 2, 4, 8
OP MODE:
HS or NC
REFRIG:
404
COND:
AC OR WC
T OP DIFF:
4
SHT CYC
3
DLY:
HPCO:
See Table-1
HPCO DLY:
10
LPCO:
See Table-1
LPCO DLY:
00:10
55
ALRM:
30
ALRM:
LOTEMP
2:00
DLY:
FAN1 ON:
See Table-1
FAN1 OFF:
See Table-1
FAN2 ON:
See Table-1
FAN2 OFF:
See Table-1
BEGIN
N/A
ALARM LIST
Nirvana Cycling Refrigerated Dryer Models 1000-1600
ingersollrandproducts.com
To enter the TECHNICIAN MODE, perform the following
keystrokes:
2
3
Pressing the "2" and "3" buttons simultaneously enters
the TECHNICIAN MODE.
SELECT
DISPLAY
Depressing SELECT DISPLAY scrolls through the
available parameters. The first three parameters viewed are
adjustable in TECHNICIAN MODE.
The DRAIN ENABLE parameter determines whether the
Microprocessor Control shall control the drain valve. A value
of "ON" will permit the Microprocessor Control to control the
drain valve. A value of "OFF" will disable this feature. Ingersoll
Rand dryers are equipped with a solenoid drain as standard
equipment. As such, DRAIN ENABLE must remain "ON"
For Ingersoll Rand dryers equipped with a NO AIR LOSS DRAIN
as equipment, DRAIN ENABLE must remain "OFF"
SELECT
DISPLAY
Depressing the SELECT DISPLAY button advances
to the next adjustable parameter for the Crankcase Heater
Delay. This parameter must not be altered unless instructed by
Ingersoll Rand Service personnel.
NOTICE
The Crankcase Heater Delay set point must not be
altered unless directed by Ingersoll Rand Service
Personnel. Improperly altering the set point may
result in damage to the dryer. Contact Ingersoll Rand
Compressed Air Solutions before altering the default
set point.
The AUTO RESTART feature permits the dryer to operate once
power is applied to the dryer without requiring operator
intervention. This would be desirable should the user wish to
have the dryer restart automatically after a power outage. To
change the AUTO RESTART set point from "N" (NO) to "Y" (YES),
perform the following. Otherwise, depress the SELECT DISPLAY
button to advance to the next display:
SELECT
AUTO RESTART: N
DISPLAY
Depressing the SELECT DISPLAY button advances to
the next adjustable parameter for the Auto Restart feature.
TECH SET
MODE
DRAIN ENABLE:
OFF
CCH DELAY: 8
17