Interruptor de transferencia automática de 30 amperios y 125 voltios

Publicidad

Idiomas disponibles

Idiomas disponibles

ATS SWITCHING TESTING:
To test the switching function after both function tests have passed:
1. Turn on the shore cord shore side breaker to engage the shower power contactor, power
is now being supplied to the RV by the shore power.
2a.Start the generator and wait for it to warm up, after 20-30 seconds you will hear a click as
the unit automatically switches over power sources from shore power to generator.
2b. Turn on the inverter you will hear a click as the unit automatically switches over power
sources from shore power to inverter.
3.Turn off shore power from the shore side breaker and confirm the generator is feeding the
line out, the power supply should not be interrupted by doing this.
4.Turn on the shore power shore side breaker again which will engage the shore power
contactor. While the shore power is still connected and on, then turn off the generator, this
will then disengage the generator contactor and automatically switch to running on shore
power feed.
CCD-0005572 Rev. 07.31.23