■ You can modify the height of the indoor unit through the
openings on the panel's four corners, if the lift of the indoor
unit and the drainpipe is not influenced.
♦
Hang the air-in grill to the panel, then connect the lead terminator of the swing motor and that of the control
box with corresponding terminators on the body respectively.
♦
Relocate the air-in grill in the procedure of reversed order.
♦
Relocate the installation cover.
- Fasten the rope of installation cover on the bolt of the installation cover. (Refer to Fig. b)
- Press the installation cover into the panel slightly. (Refer to fig. a)
Installation cover's rope
Tap screw
♦ CONNECTION OF PIPELINE
* Double-span be used when connecting the pipes.
* The wrench torque follow thw below table.
* Align the flared end of the copper pipe with the center of the theread joint. Manually tighter the flared end nut.
* Use torque spanner to tighten the flared end nut until the spanner clatters
Coat here with refrigerating machine oil
Slug
Fig. a
Pipe Outer diameter
Ф6.35
Ф9.52
Ф12.7
Ф16
Torque wrench
Spanner
Piping joint
Flare nut
Fig. b
Tightening torque N. m
15 ~ 16 N. m (153 ~ 163 kgf cm)
25 ~ 26 N. m (255 ~ 265 kgf cm)
35 ~ 36 N. m (357 ~ 367 kgf cm)
45 ~ 47 N. m (459 ~ 480 kgf cm)
Gas piping
Liquid piping
58
o L
s o
n e
p u
e p
n r
t u
Adjust lower nut
Slide the four sliders in
the corresponding
channel when installing
the cover.