A5E50802076-AB
Figure 1-2 Inserting the load voltage connection cables into the line chamber..Outer diameter of the cables > 2 mm (view from below)
It may also be the case that the minimum thread length is not observed between the individual
modules, for example when explosion-protected and standard modules are used in
combination. If the minimum thread length between conducting parts of explosion-protected
and standard modules is < 50 mm, the possibilities open to you for maintaining the thread
length between the modules are as follows:
1. Use the Ex isolating bar (6ES7 195-1KA00-0XA0) in connection with bus modules with an
active backplane bus.
2. If you do not use a bus module with an active backplane bus, you can also use the dummy
module DM 370 (6ES7 370-0AA01-0AA0).
In order to use the measurement inputs with the stated peak values for connecting to active
(remotely supplied) transmitters, the unused measurement transducer outputs 3 and 12 on the
front plug connectors must be covered with appropriate plastic caps.
When completing the wiring you must take care that there is strict separation of intrinsically
safe and non-intrinsically safe cables. They must be run in separate cable ducts.
The analog module must be operated with "safe functional extra-low voltage". This means that
even in the event of a fault these modules are exposed to a voltage of only Um ≤ 250 V.
All voltage sources, e.g. internal 24 V DC load voltage supplies, external 24 V DC load voltage
supplies or 5 V DC bus voltage, must be electrically connected to each other in such a way that
even if there are potential differences there will be no voltage addition at the individual voltage
sources, causing the fault voltage Um to be exceeded.