1. Size of BC controller's end connection piping
[Fig. 5.2.2]
TCMBG0104SJ11N4
TCMBG0106SJ11N4
(MAIN)BC
TCMBG0108SJ11N4
CONTROLLER
TCMBG1012SJ11N4
TCMBG1016SJ11N4
SUB BC
No available
CONTROLLER
072 - 120
121 - 336
337 - 432
BC CONTROLLER / MAIN BC CONTROLLER
Unit model
High pressure side*1 Low pressure side*1
TURYP/E072
ø15.88 (Brazing)
TURYP/E096
ø19.05 (Brazing)
TURYP/E120
TURYP/E144
TURYP/E168
ø22.2 (Brazing)
TURYP/E192
TURYP/E216
ø22.2(ø28.58)*2
(Brazing)
TURYP/E240
TURYP/E264
TURYP/E288
TURYP/E312
ø28.58 (Brazing)
TURYP/E336
TURYE384
TURYE432
*1. Use separately sold parts if the pipe diameter is not appropriate.
*2. If the length of high-pressure pipe A exceeds 65 m (213 ft), use the
ø28.58 (ø1-1/8) pipes for all pipes after 65 m (213 ft).
A B
C
F
*2
D
D
05-54
72-96
*1
E
A To outdoor unit (MAIN BC CONTROLLER)
B End connection (brazing)
C BC controller (MAIN BC CONTROLLER / SUB BC CONTROLLER)
D Indoor unit
E Less than 18
F Combined piping kit (Model name: CMY-R160-J1)
G Twinning pipe (Model name: CMY-Y102S-G2)
H Up to three units for 1 branch hole; total capacity: below 54 (but same in cooling/
heating mode)
The size of BC controller's branch piping is for 24 to 54 type indoor units.
Therefore, if you want to connect indoor units other than the above, connect
piping following the procedures below.
*1. For connecting 06 to 18 type indoor units
Refer to Fig. 5.2.1.
Note:
Use only the flare nuts supplied with the BC controller.
*2. To connect a unit with a capacity of higher than 54.
After combining two branches using an optionally available piping kit (CMY-
R160-J1), connect indoor units.
Available connection ( ✔ mark: available)
TCMBM0108JA11N4
TCMBM1012JA11N4
TCMBM1016JA11N4
No available
ø19.05 (Brazing)
ø22.2 (Brazing)
ø28.58 (Brazing)
ø34.93 (Brazing)
ø41.28 (Brazing)
G
D
D
D
D
H
*3
TCMBM1016KA11N4
TCMBM0108JA11N4
TCMBM1012JA11N4
TCMBM1016JA11N4
TCMBS0104KB11N4
No available
TCMBS0108KB11N4
(Qty. 1 to 11)
SUB BC CONTROLLER
Total capacity
High pressure (gas)
of indoor units
side *2
- 72
ø15.88 (Brazing)
73 - 108
ø19.05 (Brazing)
109 - 126
127 - 144
ø22.2 (Brazing)
145 - 216
217 - 234
235 - 288
ø28.58 (Brazing)
289 -
*1. The maximum total capacity of indoor units that can be connected to each Sub
BC controller is 126.
*2. Use separately sold parts if the pipe diameter is not appropriate.
*3. Connection of plural indoor units with one connection (or joint pipe)
Total capacity of connectable indoor units: Less than 54 (Less than 96 with
joint pipe)
Number of connectable indoor units: Maximum 3 Sets
Twinning pipe: Use the twinning pipe for CITY MULTI Y Series (CMY-
Y102S-G2)
Selection of refrigerant piping
Select the size according to the total capacity of indoor units to be installed
downstream.
Total capacity of indoor units
Below 54
55 to 72
73 to 96
2. Connecting to out side pipes
For TURYP072, 096, 120, 144, 168, 192, 216, 240, 264, 288, 312, 336
[Fig. 5.2.3]
High pressure/low pressure piping diagram
A
B
C
Note:
Be sure to use non-oxidative brazing.
TCMBM1016KA11N4
TCMBS0104KB11N4
TCMBS0108KB11N4
(Qty. 1 to 11)
Low pressure (gas)
Liquid side *2
side *2
ø19.05 (Brazing)
ø9.52 (Brazing)
ø22.2 (Brazing)
ø12.7 (Brazing)
ø28.58 (Brazing)
ø15.88 (Brazing)
ø34.93 (Brazing)
ø19.05 (Brazing)
ø41.28 (Brazing)
(Unit: mm [in])
Liquid line
Gas line
ø15.88 [5/8]
ø9.52 [3/8]
ø19.05 [3/4]
ø22.2 [7/8]
(Unit: mm [in])
A Connection pipe of outdoor unit
D
(Low pressure)
B Connection pipe of outdoor unit
(High pressure)
E
C Drain piping (NPT 3/4 in)
D Connection pipe of indoor unit (Liquid)
E Connection pipe of indoor unit (Gas)
13