CONTROL UNIT PROGRAMMING
The control unit has 3 keys OPEN (s), STOP (Set), CLOSE (t) that can be
used both for controlling the unit during testing and for programming the avail-
able functions .
The programmable functions available are divided into 2 levels and their rela-
Close
Open
Stop
Set
01. Press and hold down the "Set" key for approx. 3 seconds;
02. Release the key when LED L1 starts flashing;
03. Press keys "s" or "t" to move from the flashing led to the led associated with the function to be modified;
04. Press "Set" to change the status of the function: (short flash = OFF; long flash = ON)
05. Wait 10 seconds (maximum time) to exit the programming mode.
Note – During this procedure, points 03 and 04 need to be repeated when programming other functions to "ON" or "OFF" during the phase itself .
LED
Description
L1
Automatic closure
L2
Reclose after photo
L3
Always close
L4
Stand by
L5
Deceleration long
L6
Pre-flash
L7
Sensitivity
L8
Direction of motor rotation
6.2 - Level two programming (adjustable parameters)
All level 2 parameters are set by default as highlighted in grey in Table 7, and
may be modified at any time as explained in Table 8 .
The parameters can be set on a scale from 1 to 8 . To check the value corre-
sponding to each LED see Table 7 .
8 – English
tive operating status is displayed
by means of the 8 LEDs (L1...L8)
on the control unit (LED lit = func-
tion active; LED off = function not
active) .
Programming keys:
OPEN (s): the "OPEN" key ena-
bles control of pole opening or
can be used, during program-
ming, to move the programming
point up .
STOP (Set): the "STOP" key
ena-bles the user to stop the
manoeuvre; if pressed for more
TABLE 5 - Programming procedure (first level functions)
TABLE 6 - First level functions
Example
This function performs automatic closure of the pole after the programmed pause time . Factory setting:
30 seconds. Value programmable from 5 to 200 seconds.
This function enables the pole to remain in Opening position for the time required for transit . When the function is
active, operation depends on the parameter set in the function "Automatic closure":
• with "Automatic closure" active, the Opening manoeuvre stops immediately after the photocells are disengaged
and the Closure manoeuvre starts after 5 seconds .
• with "Automatic closure" not active, the pole always reaches the maximum Opening position (even if the
photocells are disengaged beforehand) and Closure starts after 5 seconds .
This function is useful in the event of a power failure, even brief . In fact if this function is active(ON), when power is
restored, the control unit detects the pole as open and starts Closure . For reasons of safety the Closure manoeuvre
is preceded by a 3-second pre-flashing interval.
The Stand-by function allows consumptions to be reduced . If active, 1 minute after the end of the manoeuvre, the
control unit turns off the "Bluebus" output (connected devices) and all the LEDs apart from the Bluebus LED which
will flash more slowly. When the control unit receives a command normal operation is restored. When using S4BAR
with the Solemyo system, a longer Stand By mode must be set . This operation is performed using the Oview
programmer .
This function enables the user to double the space for starting deceleration, both in Opening and Closing . If the
function is deactivated, deceleration is short .
This function activates a pause of 3 seconds between activation of the flashing light and the start of a manoeuvre.
When this function is set to "ON" the level of control unit sensitivity in obstacle detection can be increased
considerably . If used as a means to read the "impact force" of the motor, the values "speed" and "motor force"
must be set accordingly in the level 2 menu .
This parameter enables inversion of the direction of motor rotation to enable barrier installation on the right; the
factory setting is "OFF" (standard motor rotation – pole closure on left) .
Important – If the function is activated, the Opening and Closing positions must be memorised again (Paragraph 4 .5) .
than 5 seconds, it enables entry to programming mode .
CLOSE (t): the "CLOSE" key enables control of pole closing or can be used,
during programming, to move the programming point down .
CAUTION! – During a manoeuvre (Open or Close) all three keys have
the STOP function: all manoeuvres in progress are stopped.
6.1 - Level one programming (ON-OFF functions)
All level 1 functions are set by default to "OFF" and may be modified at any
time as explained in Table 5 . To check the value corresponding to each LED
see Table 6 .
IMPORTANT – The programming procedure has a maximum interval of 10
seconds admissible between the activation of one key and the next. When this
time interval elapses, the procedure quits automatically, saving the changes
made up until that time .
IMPORTANT – In the programming procedure, the maximum time interval
that can elapse between activation of one key and the next is 10 seconds.
When this time elapses, the procedure terminates automatically, memorising
the modifications made up until then.
SET
3 s
L1
SET
/
SET
10 s