Illustration 2.9: AC Cable
AC Cable Requirements
A total loss of 1% is recommended when dimensioning the AC cables, between the inverters and
energy-meter. The cable cross-sections specified below are recommended for cable lengths up to
10 m.
Specification
When selecting cable for the AC installation, ensure to comply with local and national regulations.
Recommended mini-
> 1.5 mm
mum cable require-
lated, approved house
ments (PVC coated
wire)
Indoor use
Temperature range
Extended temperature
range
Indoors ⌀ max.
Table 2.2: AC Cable Requirements
Fuses
The main purpose of the fuse is to protect the installation against short circuits. It is recommended
to use a slow fuse, class C. When selecting the fuse for the AC installation, ensure to comply with
local and national regulations.
PowerStocc
PowerStocc
1200 / 2000
3000 / 4000
2
double insu-
> 2.5 mm
sulated, approved
wiring cable
house wiring cable
≥500 [V]
≥500 [V]
0 - +60°C
0 - +60°C
0 - +90°C
0 - +90°C
10 mm
10 mm
L00410289-03_3m
2. Installation and Setup
PowerStocc
5000 / 6000
2
double in-
> 4.0 mm
2
double in-
sulated, approved
house wiring cable
≥500 [V]
0 - +60°C
0 - +90°C
10 mm
2
11