en
Relay inactive delay
Resetting the signal is delayed after a fault, warning message or a change in the operating status has been
rectified. Select menu:
The inactive delay prevents flickering of the signal when states occur very briefly and can be set between
0 ... 60 seconds.
NOTICE
Active and inactive delay are set in the factory to 5 seconds.
8.1.4.2 Relay test mode
The module offers the possibility of checking the wiring of the relay output and the reaction of connected
technology (e.g., during commissioning).
Regardless of the state of the pump, the relay state can be overridden and forced for a limited time. The set-
ting is made via the operating elements of the pump. Select menu:
The forced state is active for approx. 15 minutes. After expiry, the mode automatically returns to "normal".
Before these 15 minutes have expired, "Normal" can also be selected again in the menu.
Forced inactive
The relay switching state is forced INACTIVE.
The contact between COM and NO is open; the contact between COM and NC is closed.
46
The triggering of the respective signal after the occurrence of a
fault, a warning or an operating state is delayed.
The active delay can be set between 0 ... 60 seconds.
If states are no longer present before the set time has elapsed,
they are not reported.
A set active delay of 0 seconds reports states immediately.
WCM BMS
WCM BMS
Normal (factory setting)
The relay signals the operating state as set in the SSM/SBM con-
figuration.
Forced active
The relay switching state is forced ACTIVE.
The contact between COM and NO is closed; the contact
between COM and NC is open.
Installation and operating instructions • Wilo-Connect module BMS • Ed.02/2023-10
R. inact. delay
Relay test ctrl