Maximum Single Pipe Length: 100m (Class C)
Maximum Branched Pipe Length: 200m (2 x 100m, Class C)
Maximum Number of Holes: See Table 1A
Pipe Spec (EN54-20 Compliance): to EN 61386
Outside Pipe Diameter:
Shipping Weight:
50 mm
60 mm
110 mm
356 mm
Figure 1: Dimensions and Knock-Outs
PHYSICAL INSTALLATION
Front Panel Labels
The LT-200 NFXI-ASD is shipped without the front panel labels fixed in
place. This allows the installer to choose the language required for the
installation from the Front Panel Labelling Pack.
Figure 2 shows where the labels need to be placed:
ALARM
PREALARM
10
10
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
SMOKE
1
1
LEVEL 1
MODULE 1
FAULT
A
When label A is in place, remove the protector from the bottom of the
clear cover to stick the cover down, as shown in Figure 3:
N200-102-01
(Crush 1, Impact 1, Temp 31)
25mm (nom) or 27mm (nom)
6.5kg (inc sensors)
50 mm
65 mm
90 mm
SMOKE
LEVEL 2
MODULE 2
POWER
FAULT
Figure 2:
Placing the Front Panel Labels
26 mm
Cable Access
Knock out cable gland holes where
required. The location of the cable
gland holes is shown in Figure 1,
represented by the icon:
Mounting the LT-200 NFXI-ASD to the Wall
26 mm
FAAST LT
HANGING LUGS
135 mm
POSITION OF BRACKET
PLUMB LINE
OUTER DIMENSION OF UNIT
212 mm
* Minimum clearance required from hinges to open door = 35 mm.
Figure 6: Fasten the mounting bracket to the wall
2
Figure 3:
Remove Backing to
Stick Cover Down
How to Knock Out
Cable Gland Holes
INDICATES CENTRE OF ASPIRATING PIPES
FIXING HOLE
USE FOR PLUMB-LINE
Figure 5: Mounting Bracket
90 mm
99 mm
BASE OUTLINE
144 mm
Figure 4:
FIXING HOLE
59
41
mm
mm
*
329
mm
*
I56-6577-008