–
display.High allows
defining the maximum value to be
displayed. This value corre-
sponds to the value ou.Hi used
for the output setpoint.
Example:
The display must show 10 (kg) while
the setpoint output must be 2 V
(lower limit value); the display must
show 40 (kg) while the setpoint out-
put must be 8 V (upper limit value).
7
D
6
A
8 V
2 V
10 kg
3. Press both keys to resume pro-
gramming at point 4.2.2 (1), SiGn
see A in the flow chart
⇑
⇑
Summary:
Display
When programming, the values for
the display and for the output set-
point are linked internally together.
8
40 kg
Output value
Note:
When the SPecial display function is
activated, the increment relates to
the value scaled in the MAn opera-
ting mode.
4.2.3 The Auto Operating Mode
1. The following parameters can be
programmed for the Auto mode:
1 sec
A
see 4.2.3.1
to
to
to
to
to
to