2.5 Connection with a FlexPDU (Power Distribution Unit) module (optional)
2.6 Connection with a HotSwap MBP module (optional)
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads
(HotSwap function).
2. Installation
1 - PW5130 2500 / 3000: connect the UPS
input socket (10) to the AC-power source
using the cable (31) supplied.
PW5130 1250 / 1750 : use the power cable of
the protected equipment.
2 - PW5130 2500 / S 3000: connect the input
socket on the FlexPDU module (48) to the
UPS outlet (7) using the cable (41) supplied.
PW5130 1250 / 1750 : connect the input
socket on the FlexPDU module (48) to one of
the outlets (9).
The cable and the connectors are marked in
red.
3 - Connect the equipment to the outlets (45),
(46) and (47) on the FlexPDU module. These
outlets differ, depending on the version of the
FlexPDU module.
4 - Fit the connection securing system that
prevents the plugs from being pulled out
accidentally.
1 - Connect the input socket (56) on the
HotSwap MBP module to the AC-power
source using the cable (31) supplied.
2 - Connect the UPS input socket (10) to the
"UPS Input" (55) on the HotSwap MBP
module, using the cable (44) supplied. These
cables and the connectors are marked blue.
3 - PW5130 2500 / 3000: connect the UPS
outlet (7) to the "UPS Output" (54) on the
HotSwap MBP module, using the cable (44)
supplied.
PW5130 1250 / 1750 : connect one of the
UPS outlets (9) to the "UPS Output" (54) on
the HotSwap MBP module.
These cables and the connectors are marked
in red.
4 - Connect the equipment to the outlets (49)
and (50) on the HotSwap MBP module.
These outlets differ, depending on the
version of the HotSwap MBP module.
Caution. Do not use UPS outlets (8) and (9)
to supply equipment because use of
switch (53) on the HotSwap MBP module
would cut supply to the equipment.
MAU-00069 AA
- Page 11