7. Connecting refrigerant pipes and drain pipes
7.1. Refrigerant piping work
This piping work must be done in accordance with the installation manuals for both
outdoor unit and BC controller (simultaneous cooling and heating series R2).
•
Series R2 is designed to operate in a system that the refrigerant pipe from an
outdoor unit is received by BC controller and branches at the BC controller to
connect between indoor units.
•
For constraints on pipe length and allowable difference of elevation, refer to the
outdoor unit manual.
•
The method of pipe connection is brazing connection.
Caution:
•
Install the refrigerant piping for the indoor unit in accordance with the
following.
1. Cut the tip of the indoor unit piping, remove the gas, and then remove the brazed
cap.
[Fig. 7.1.1] (P.4)
Cut here
A
Remove brazed cap
B
2. Pull out the thermal insulation on the site refrigerant piping, braze the unit piping,
and replace the insulation in its original position.
Wrap the piping with insulating tape.
Note:
•
When blazing the refrigerant pipes, be sure to blaze, after covering a
wet cloth to the pipes of the units in order to prevent it from burning and
shrinking by heat.
[Fig. 7.1.2] (P.4)
Cool by a wet cloth
A
•
Pay strict attention when wrapping the copper piping since wrapping the
piping may cause condensation instead of preventing it.
[Fig. 7.1.3] (P.4)
Thermal insulation
A
Wrap with damp cloth
C
Ensure that there is no gap here
E
Cautions On Refrigerant Piping
► Be sure to use non-oxidative brazing for brazing to ensure that no foreign
matter or moisture enter into the pipe.
► Be sure to apply refrigerating machine oil over the flare connection seating
surface and tighten the connection using a double spanner.
► Provide a metal brace to support the refrigerant pipe so that no load is
imparted to the indoor unit end pipe. This metal brace should be provided
50 cm away from the indoor unit's flare connection.
Warning:
Do not use refrigerant other than the type indicated in the manuals provided
with the unit and on the nameplate.
- Doing so may cause the unit or pipes to burst, or result in explosion or fire during
use, during repair, or at the time of disposal of the unit.
- It may also be in violation of applicable laws.
- MITSUBISHI ELECTRIC TRANE HVAC US LLC cannot be held responsible for
malfunctions or accidents resulting from the use of the wrong type of refrigerant.
Caution:
•
Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized
copper as specified in the JIS H3300 "Copper and copper alloy seamless
pipes and tubes". In addition, be sure that the inner and outer surfaces
of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt,
shaving particles, oils, moisture, or any other contaminant.
•
Never use existing refrigerant piping.
- The large amount of chlorine in conventional refrigerant and refrigerator oil in
the existing piping will cause the new refrigerant to deteriorate.
•
Store the piping to be used during installation indoors and keep both ends
of the piping sealed until just before brazing.
- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and
the compressor may fail.
•
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil
to coat flares and flange connections. (For models using R410A or R407C)
- The refrigerant used in the unit is highly hygroscopic and mixes with water and
will degrade the refrigerator oil.
Pull out insulation
B
Return to original position
D
Wrap with insulating tape
F
7.2. Drain piping work
•
Ensure that the drain piping is downward (pitch of more than 1/100) to the
outdoor (discharge) side. Do not provide any trap or irregularity on the way.
•
Ensure that any cross-wise drain piping is less than 20 m [65 ft] (excluding
the difference of elevation). If the drain piping is long, provide metal braces to
prevent it from waving. Never provide any air vent pipe. Otherwise drain may be
ejected.
•
Use a hard vinyl chloride pipe O.D. ø32 mm [1-1/4 in] for drain piping.
•
Ensure that collected pipes are 10 cm [3-15/16 in] lower than the unit body's
drain port.
•
Do not provide any odor trap at the drain discharge port.
•
Put the end of the drain piping in a position where no odor is generated.
•
Do not put the end of the drain piping in any drain where ionic gases are
generated.
[Fig. 7.2.1] (P.4)
○
Correct piping
×
Wrong piping
Insulation (9 mm [3/8 in] or more)
A
Downward slope (1/100 or more)
B
Support metal
C
Air bleeder
K
Raised
L
Odor trap
M
Grouped piping
O.D. ø32 mm [1-1/4 in] PVC TUBE
D
Make it as large as possible. About 10 cm [3-15/16 in].
E
Indoor unit
F
Make the piping size large for grouped piping.
G
Downward slope (1/100 or more)
H
O. D. ø38 mm [1-1/2 in] PVC TUBE for grouped piping. (9 mm [3/8 in] or more
I
insulation)
Up to 700 mm [27-9/16 in]
J
Drain hose (accessory)
N
Horizontal or slightly upgradient
O
1. Insert the drain hose (accessory) into the drain port (insertion margin: 32 mm
[1-1/4 in]).
(The drain hose must not be bent more than 45° to prevent the hose from
breaking or clogging.)
(Attach the hose with glue, and fix it with the band (accessory).)
2. Attach the drain pipe (O.D. ø32 mm [1-1/4 in] PVC TUBE PV-25, field supply).
(Attach the pipe with glue, and fix it with the band (accessory).)
3. Perform insulation work on the drain pipe (O.D. ø32 mm [1-1/4 in] PVC TUBE
PV-25) and on the socket (including elbow).
4. Check the drainage. (Refer to [Fig. 7.3.1])
5. Attach the insulating material, and fix it with the band (accessory) to insulate the
drain port.
[Fig. 7.2.2] (P.4)
Indoor unit
A
Tie band (accessory)
B
Visible part
C
Insertion margin
D
Drain hose (accessory)
E
F Drain pipe (O.D. ø32 mm [1-1/4 in] PVC TUBE, field supply)
G Insulating material (field supply)
Tie band (accessory)
H
11