I N S TA L L ATI O N G U I D E
WIRING THE FIXTURES
2. Connect the leader cable to the first
fixture in the run.
3. Cut off the unused end of the leader
cable and strip back the black jacket of the
cable to expose the insulated wire inside.
4. Install this end of the cable into a
junction box and splice to building power
and control wires per NEC and local
standards. See table below for wire color
assignments.
NOTE: For Class 2 control systems the
line-voltage wires must be separated
from the Class 2 control wires with an
insulated divider (by others).
5. To install the next fixture in the
run, connect the integral electrical
connectors from one fixture to the next.
6. Install Jumper Cables between fixtures
if needed.
7. Screw the fixture in place using step 1.
8. Repeat Steps 1 to 6 for the remaining
fixtures.
9. On the last fixture in the run install the
terminator caps to the end connector.
L45 and L60 Wiring Assignments
Line Voltage
Control Wires
120-277VAC 50/60Hz
ELV
Brown - Hot/Line
Not Used
0-10V
Blue - Neutral
Green - Ground
Violet - Dim1 +
Pink - Dim -
Orange - Dim2 +
DALI
Violet - DA
Pink - Not Used
Orange - DA
DMX
Violet - Data 1+
Pink - Data Link
Common
Orange - Data 1-
®
2. Connectez le câble de tête au premier
luminaire.
3. Coupez l'extrémité inutilisée du câble de tête
et dénudez la gaine noire du câble pour exposer
le fil isolé à l'intérieur.
4. Installez cette extrémité du câble dans
une boîte de jonction et raccordez les fils
d'alimentation et de commande du bâtiment
conformément aux normes NEC et locales. Voir
le tableau ci-dessous pour le branchement des
fils par couleur.
REMARQUE : pour les systèmes de commande
de classe 2, les fils de tension de ligne doivent
être séparés des fils de commande de classe 2
par un diviseur isolé (par d'autres).
5. Pour installer le luminaire suivant, connectez
les
connecteurs
luminaire à l'autre.
6. Installez les câbles de raccordement entre les
luminaires si nécessaire.
7. Vissez le luminaire en place en suivant l'étape 1.
8. Répétez les étapes 1 à 6 pour les autres
luminaires
9. Sur le dernier luminaire, installez les capuchons
de terminaison sur le connecteur d'extrémité.
Male Terminator Cap
ECOSENSE LIGHTING INC.
837 NORTH SPRING STREET
SUITE 103
LOS ANGELES, CA 90012
électriques
intégrés
d'un
Jumper Cable
Leader Cable
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE. VISIT
P • 310 . 496 . 6255
ECOSENSELIGHTING.COM FOR THE MOST CURRENT SPECIFICATIONS.
F • 310 . 496 . 6256
© 2019 ECOSENSE LIGHTING INC. ALL RIGHTS RESERVED. ECOSENSE,
THE ECOSENSE LOGO, RISE, TROV, SLIM COVE AND ECOSPEC ARE
T • 855 . 632 . 6736
REGISTERED TRADEMARKS OF ECOSENSE LIGHTING INC.
FREEDOM TO CREATE™
I NTERI O R + E X TER I O R | L45
2. Conecte el cable guía al primer dispositivo en
el tramo.
3. Corte el extremo sin usar del cable guía y pele
el plástico negro del cable para exponer el cable
aislado en su interior.
4. Instale este extremo del cable en una caja de
conexiones y empalme a los cables de control y
a la alimentación del edificio según las normas
locales y el NEC. Consulte la tabla de abajo para
ver las asignaciones de color de los cables.
NOTA: en el caso de los sistemas de control de
clase 2, los cables de tensión de línea deben
estar separados de los cables de control de
clase 2 con un separador aislado (por otros).
5. Para instalar el siguiente dispositivo en
el tramo, conecte los conectores eléctricos
integrales de un dispositivo al siguiente.
6. Instale pinzas entre los dispositivos si las
necesita.
7. Atornille el dispositivo en su lugar usando el
paso 1.
8. Repita los pasos 1 a 6 para los dispositivos
restantes.
9. Instale el tapón de terminación al conector
final en el último dispositivo del tramo.
3/5
20230801