Force Adjustment - Telcoma EVO600 Instrucciones De Uso Y De Programación

Motorreductores de 230v para hojas de corredera
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 23
GB
CONFIGURATION DIP-SWITCHES
Select the options required and perform a reset (part. 15, fig. 1) to render the changes operational.
Function
n. Off On Descrption
Step-by-step
input
and
radio channel
mode (CH1)
Jolly
input mode
Preflash
Re-closure
Timer
Photo test
Brake
Slowdown
Reclosing after
the
photoelectric
cells

FORCE ADJUSTMENT

EN 12445 requires that every automation system must pass impact tests measured with a special instrument.
Carry out the impact tests and change the encoder sensitivity through the trimmer (part 8 fig. 1).
If adjustments are insufficient to make values fall within the graph indicated by the above standard, we recommend installing a soft
rubber profile on the leading edge of the gate in order to soften impact.
If the requirements of the standard can still not be met after having adjusted the sensitivity and mounted the rubber profile, alternative
devices must be mounted, such as a safety edge on the leading edge of the gate.
SOFT START
The soft-start function determines a gradual start of movement without jolts on the gate. This function may in any case be bypassed
by inserting the jumper Jp1 (part 9 of Fig. 1).
Attention: by activating jumper Jp1 the motor force will always be at the maximum.
35
Open - Stop -
During opening, upon pressing the P/P button the gate stops, pressing it again the gate closes.
Close
During closing, upon pressing the P/P button the gate stops, pressing it again the gate opens.
During opening, upon pressing the P/P button the gate stops for a few seconds and then closes.
Open - Close
During closing, upon pressing the P/P button the gate stops for a few seconds and then opens.
During opening, pressing the P/Pbutton has no effect. During the pause, pressing the P/Pbutton has no
Always opens
effect.
"Condominium"
During closing, upon pressing the P/P button the gate stops for a few seconds and then opens.
Opens-Closes
During opening, pressing the P/Pbutton has no effect. During the pause, upon pressing the P/Pbutton the
with no reversal
gate closes.
during opening
During closing, upon pressing the P/P button the gate stops for a few seconds and then opens.
Safety edge activation reverses the direction for a few seconds. After safety edge activation the control
Safety edge
unit locks; re-closing is cancelled. Use a N.C. contact
Clock
Closes the gate when the contact is opened and opens when the contact is closed.
During both opening and closing, activation of this photocell stops the gate until it is reset.
Photocell
The next movement is always in the opening direction. Use a N.C. contact
Pedestrian
The gate open spartially for a programmable time (see"pedestrianopeningprogramming").
access
Use a N.O.contact.
OFF
The flashing light operates together with the motor.
ON
The flashing light operates 5 seconds before any operation.
OFF
After one complete opening, the control unit only closes again with a manual control.
ON
After one complete opening, the control unit closes automatically after the programmed pause time.
OFF
ON
See text at page 42.
OFF
ON
The m. brake serves to overcome the inertia of heavy aut. systems. When the brake is enabled it activates
at the end of every m
OFF
There is no slowdown in the last part of travel.
ON
With the slowdown function connected, the motor halves its speed towards the end of every gate movement.
OFF
ON
The activation of photoelectric cell reduces the pause time for whatever is value previously was to 2
seconds.
Notes

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Evo800Evo1200Evo1200r

Tabla de contenido