CERTIFIED APPLICATIONS
Deck-mounted basin version
WRAS Approval No: 1907015
NSF Certification Number: BC1002/0512
Certified Applications
H9600 Flexible tails fixed
H9605 Flexible tails Bioclip
H9600610 Copper tails fixed
H9605610 Copper tails Bioclip
Complies with the NHS Model Specification D08, designation HP - WE when operated as set
out in table below.
Operating Pressure Range
Maximum pressure - bar
Flow Pressure, Hot and Cold - bar
Hot Water Supply Temperature -°C
Cold Water Supply Temperature - °C
Mixed Water Temperature - °C
OPERATION (FIG. B)
• In position b, the single lever sequential thermostatic mixer is closed.
• When the control lever a is turned clockwise, the mixer will start to deliver cold water at
the temperature of the cold water supply in position c. Continue turning the control lever a,
and the water will get progressively hotter up to position d, which is the maximum hot water position.
• The maximum temperature is pre-set at the factory between 39°C and 41°C with the following
parameters: hot and cold water pressures are balanced at 3 bar dynamic pressure; hot water
temperature at 65°C +/- 5°C; and cold water temperature at 15°C +/-5°C.
TECHNICAL CHARACTERISTICS (FIG. B)
Flow rate:
• For basin mixers H9600/H9605:
Mixed Water temperature at 39°C at 3 bar pressure: 5 lpm.
• For sink mixers H9620/H9625:
Mixed Water temperature at 39°C at 3 bar pressure: 9 pm.
Safety:
• If the cold or hot water fails, the mixed water will shut off within 2 seconds.
• The anti-scalding safety is active if the temperature differential between the hot water and mixed water
is more than 15°C
• Check the anti-scalding failsafe every two months and as often as necessary depending on the water
quality. Shut off the cold water and check that the hot water stops within 2 seconds.
When using a filtration device or similar system at the spout outlet or shower head, the flow rate must be
higher than 4 litres per minute to avoid cross flow between the hot and cold water.
Note: The anti-scalding safety is active if the cold water supply fails. If, instead of cold water, hot water
returns through another mixer, there is no anti-scalding safety. We recommend installing a non-return
valve on the cold water supply to the mixer.
High Pressure Systems
10
1 to 5
55 to 65
5 to 20
40.5
Low Pressure Systems
10
0.2 to 1
55 to 65
5 to 20
40.5