MAINTENANCE
• Check the calibration at least twice a year (Fig. C & D).
• We recommend checking the anti-scalding failsafe every two months and as often as necessary depending
on the water quality. Shut off the cold water and ensure that the hot water stops within 2 seconds.
• To maximise the reliability of SECURITHERM thermostatic mixing valves over time, and to reduce
the risks associated with Legionella, we recommend an annual check of the following items:
1. Inter-changeable cartridge: de-scale internal parts and replace worn or damaged parts.
2. Mixing chamber: de-scale.
3. Replace the control lever and tighten to 13 Nm +/-1 (Fig. F).
• In the event cartridge malfunction, please replace (Fig. G).
• We recommend checking that the thermostatic cartridge en "seats" are waterproof twice a year
and as often as necessary depending on the water quality.
To check the seats:
1. Shut off the hot water: check that there is no cross flow of cold water into the hot water system.
2. Shut off the cold water: check that there is no cross flow of hot water into the cold water system.
If there is cross flow, clean the seats or replace the thermostatic cartridge.
MAINTENANCE & CLEANING
• Cleaning chrome, aluminium and stainless steel: do not use abrasive, chlorine or any other acid-
based cleaning products. Clean with mild soapy water using a cloth or a sponge.
• Frost protection: drain the pipes and operate the mixer/tap/valve several times to drain any
remaining water. In the event of prolonged exposure to frost, we recommend taking the mechanisms
apart and storing them indoors.
For the UK market only: Tel. 01491 821 821 - email: technical@delabie.co.uk
For all other markets: Tel. +33 (0)3 22 60 22 74 - email: sav@delabie.fr
After Sales Care Support:
The installation guide is available on: www.delabie.co.uk