Overload capacity
Batteries
Number of batteries
Battery type
Battery voltage/capacity
Backup time
Protection
Typical recharge time
Communication and management
Interface
USB HID
Alarms
Mechanical characteristics
Dimensions W x H x D (mm)
Net weight (kg)
Environmental conditions
Operating temperature (°C)
Operating relative humidity
Storage temperature (°C)
Noise level at 1 m
IP code
Reference directive and standards
Safety
EMC
3 101 80
3 101 83
3 101 81
3 101 84
3 101 82
3 101 85
during normal mode:
automatic shutdown after 5 minutes with load>100%
automatic shutdown after 5 seconds with load>120%
immediate shutdown for short-circuit
during battery mode:
immediate shutdown
1
6-cell VRLA (valve-regulated lead-acid), maintenance free
12Vdc -
12Vdc -
7 Ah
9 Ah
10 min. (calculated with one typical workstation)
against total discharge
two pushbuttons and four LEDs
Visual (LEDs), Audible (buzzer)
20 x 138 x 330
4.8
5.5
<95% (non-condensing)
2014/35/EU Directive
2014/30/EU Directive
EN 62040-2 (category C2)
3 101 86
3 101 89
3 101 87
3 101 90
3 101 88
3 101 91
2
12Vdc -
7 Ah
4-6 hours
type B
148 x 173 x 380
8.3
9.6
0 to +40
+20 to +25
< 40 dB
IP 20
EN 62040-1
KEOR SP
3 101 92
3 101 93
3 101 94
12Vdc -
9 Ah
10.3
37