Quick Start Guide
English
Features
•
0-10 V or 4-20 mA output, active, power supply
24 Vac/Vdc (3-4 wires) or 4-20 mA output, passive
loop, power supply from 16 to 30 Vdc (2 wires)
•
ABS V0 housing, IP65, with or without display
General features
Output / Supply
Consumption
European directives
Electrical connection
PC Communication
Environnement
Response time
Zero setting
Type of fluid
Conditions of use
(°C/%RH/m)
Storage temperature
*All the accuracies indicated in this technical datasheet were stated in laboratory conditions, and can be guaranteed for measurements carried out in the same conditions, or carried out with calibration compensation.
Differential pressure
transmitter
Ranges from -100/+100 Pa to
-2000/+2000 mbar (according to model)
Configurable intermediary
ranges
•
"¼ turn" system mounting with wall-mount plate
•
Housing with simplified mounting system
•
Solenoid valve for auto-calibration (only on
CP 111 model)
Active sensor 0-10 V or 4-20 mA (alim. 24 Vac/Vdc ±10%), 3-4 wires
Passive loop 4-20 mA (power supply 16/30 Vdc), 2 wires
Common mode voltage <30 VAC
Maximum load: 500 Ω (4-20 mA) / minimum load: 1 K Ω (0-10 V)
CP 111: 3 VA (0-10 V) or 3 VA (4-20 mA)
CP112, CP113, CP 114, CP 115: 2 VA (0-10 V) or 0.6 VA (4-20 mA)
2014/30/EU EMC; 2014/35/EU Low Voltage; 2011/65/EU RoHS II; 2012/19/EU WEEE
Screw terminal block for cables from 0.05 to 2.5 mm
Carried out according to the code of good practice
Manual autozero with push-button; self-calibration by solenoid valve (CP 111 only)
Air and neutral gases
From 0 to +50 °C. In non-condensing condition. From 0 to 2000 m
From -10 to +70 °C
or from 30 to 14 AWG
2
USB-mini DIN cable
Air and neutral gases
1/e (63%) 0.3 s