44 WARNING
Turn off electricity at the service
panel
before
wiring
the
unit.
(See
Safety
instructions, Page 1).
Wiring the Hood with an
Integral Motor
1.
Remove the j-box cover.
2.
Connect the VTN1030C molex plug connector to
the connector present inside the hood as shown
in Figure 13.
3.
Install 1/2" conduit connector in |-box.
From Ventilator
From Control Panel
Figure 13
4.
Run black, white, and green wires (#12 AWG)
in
1/2" conduit from power supply to J-box.
5.
Connect the power supply wires to the hood
wires in the following order: black to black, white
to white, and green wire to green ground screw
on chasis. Use spring type wire nuts supplied.
(Lost or missing wire nuts should only be
replaced with: Spring type wire nuts rated fora
minimum of (2) # 18ga wires and maximum of
(4) #14ga wires, UL & CSA rated to G00V and
302 deg. F./150 deg. C).
6.
Close J-box cover.
Check to see that light bulbs
are secure in their sockets. Replace filters as
described in the Care & Use Manual. Turn power
on at service panel. Check operation of the
hood.
Remote
Blower Installation
The PH hood models are designed to work with
VTR630D, VTR1030D, VTR1330E, or VTR1530D
remote blowers. For installation instructions see the
instructions supplied with the blower unit.
11
Wiring the Hood with a
Remote Blower
corohoed Be)
W
Bk 1°
3A
o
2
4
SF q
@)
w
[Bt IR
iD
DB)
sD
REMOTE
\BL
VENTILATOR
Figure 14
Remove the J-box cover.
install 1/2" conduit connectors.
Run black, white, and green wires (#12 AWG)
in
1/2" conduit from power supply to j-box.
Connect the power supply wires to the hood
wires in the following order: black to black, white
to white, and greenwire to green ground screw
on chassis. Use spring type wire nuts supplied.
(Lost or missing wire nuts should only be
replaced with: Spring type wire nuts, rated fora
minimum of (2) # 18ga wires and maximum of
(4) #14ga wires, UL & CSA rated to 600V and
302 deg. F./150 deg. C).
Connect the "pigtail" to the connector inside the
junction box.
Run five (5) wires (#14 AWG)
in 1/2" conduit
from the remote blower to the second conduit
connector.
Connect the remote ventilator to the pigtail wires
(Step 6) as per Figure 14. Connect the remote
blower green (ground) wire to the ground screw
in the junction box.
Close junction box cover. Check thai all light
bulbs are secure in their sockets. Install filters.
Turn power on at service panel, and check lights
and blower operation per Care & Use Manual.