Descargar Imprimir esta página

System Sensor OSI-RIE- Serie Guia De Inicio Rapido página 3

Detector de haz lineal de imágenes de humo (tipo de haz de luz proyectado), inteligente

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 15
QUICK START GUIDE
OSI-RIE-xx
Smoke Imaging Linear Beam Detector
(Projected Beam Type), Intelligent
SPECIFICATIONS
Wire Gauge for Terminals:
Operating Voltage Range:
Maximum Standby Current:
Maximum Alarm Current (LED on):
Operating Humidity Range:
Operating Temperature Range:
Adjustment Angle:
Sensitivity Levels:
Fault Condition (Trouble):
IP Rating:
Alignment Aid:
Alarm Indicator:
This guide provides information on how to install the OSI-RIE-xx Smoke Detection
System.
Extensive product and critical product security information can be found in the
OSI-RIE-xx Installation Guide (Document No. E56-6965) available at
systemsensoreurope.com/products/intelligent-beam-detectors-osi-rie-xx/.
The OSI-RIE-xx system consists of an Imager and a reflector. (See Figure 1.)
The products shall be powered from a EN54-4 certified AC/DC Power converters to
be in compliance for CE certification.
FIGURE 1. IMAGER AND REFLECTOR
DETERMINE THE POSITIONS OF THE IMAGER AND REFLECTOR
COMPONENTS
Make sure that the intended mounting locations meet the following criteria (See Fig-
ure 2.):
• Detector spacing must comply with local codes and standards
• Reflector must be located within the Field of View (FOV) of the Imager
• Clear path between the reflector and Imager
• Mounted well above the head-height of people and obstructions
• Avoid direct sunlight onto the units
The Imager and reflector should be placed within a recommended distance below
the ceiling. (See Figure 3.) This value will vary according to regional specifications,
geometry, and specific requirements for the installation. The distance for flat ceilings
and basic spacing requirements (S) is shown in the following table.
Standard
Distance from Ceiling
NFPA 72
300 mm (12 in.) minimum
AS1670.1
25 to 600 mm (1 to 23.6 in.)
BS5839.1
25 to 600 mm (1 to 23.6 in.)
GB50166
300 to 1000 mm (11.8 to 39.4 in.)
For full information on spacing requirements, please refer to your local codes and
standards.
22 AWG (0.64 mm, 0.34 mm2) to 14 AWG (1.6 mm, 2.08 mm
Without isolator: 15 to 32 VDC
With isolator: 15-28.5V
13 mA @ 32 VDC, 14 mA @ 24 VDC, 20 mA @ 15 VDC
22 mA @ 32 VDC, 15 mA @ 24 VDC, 22 mA @ 15 VDC
0% to 95% Relative Humidity, Non-condensing
–4°F to 131°F (-20°C to +55°C). UL-Listed for use from 32°F to 100°F (0°C to 37.8°C)
20 degrees vertical, 50 degrees horizontal
Level 1 25%, Level 2 30%, Level 3 40%, Level 4 50%
Long-term drift reference out of 20% range, beam blockage or detector out of alignment, imager saturated.
IP 55. This beam detector is IP55 rated, therefore an IP55 compliant cable gland suitable to wire gauge must be used
LED directional arrows
Local red LED and remote output
https://www.
C2051-00, C2052-00
Maximum Spacing (S)
18.3 m (60 ft)
14 m (45.9 ft)
15 m (49.2 ft)
14 m (45.9 ft)
2
)
OSI-RIE-xx Quick Start Guide applies to the model OSI-RIE-SS and models where
-xx is replaced by numerals, i.e. OSI-RIE-6.
FIGURE 2. MOUNTING LOCATIONS
1/2 S
12" minimum
(0.3m)
30' (9.1m) maximum
To First
Detectors
10' (3.0m)
Wall
minimum
Typical
FIGURE 3. MOUNTING LOCATIONS
Ex. Distances according to NFPA 72.
Tx/Rx
1/4 S
maximum
Tx/Rx
1
Pittway Tecnologica S.r.l.,
Via Caboto 19/3,
34147 TRIESTE, Italy
S
1/2 S maximum
Reflector
S
Reflector
16 ft. (5m) minimum
328 ft. (100m) maximum
I56-6965-001
01/16/2023
C2053-00
C2054-00

Publicidad

loading

Productos relacionados para System Sensor OSI-RIE- Serie