ARES UPS User Manual
Operation
LCD panel
Line mode start up
1. Please ensure the outlet of power source is proper grounded.
2. Ensure the voltage rating of power source is matched with UPS spec.
3. Plug in UPS to the AC source
4. UPS will start initializing after AC input power is available 5 seconds. LED/LCD indicator will be all lit
and dim once and fan will start spinning. Full LCD display looks as below figure:
Press UPS
button and hold untill twice beep heard, UPS begins starting procedures for 5 seconds.
LCD display will show as below figure-A and then figure-B sequentially. When you see figure-B means the
starting up procedure is finished
Start-up in Battery Mode (Cold Start)
1. Ensure the internal battery is available or external battery set well connected to UPS. Press and hold
key for 3 seconds until twice beeps heard, release button and press
beeps heard again to confirm cold start procedure. If the 2nd button confirmation not be finished
within 10 seconds after 1st twice beeps, UPS will not cold start and shut off after 10 seconds.
2. 5 seconds after cold starting, intermittent audible alarm will be heard and LCD will show sequentially
as below figure-D and figure-E.
Note: Ensure that the UPS batteries are pre-charged for at least four hours by simply connecting the AC
power cord to the utility receptacle.