Installation
Safety Information
To ensure proper operation:
Installation
This fixture has been designed and 3rd party tested to meet ANSI/ISEA Z358.1. The system must be tested
periodically to be sure it is functioning properly to meet the standard. Please refer to the ANSI/ISEA Z358.1
standard on testing requirements.
The installation, maintenance and location of all safety drench showers, eye and eye/face washes must comply
with the requirements of ANSI/ISEA Z358.1. Workers who may come in contact with potentially hazardous
materials should be trained regarding the location and proper operation of emergency equipment per ANSI/ISEA
Z358.1.
ANSI/ISEA Z358.1 requires this unit to be used with a clean, potable, uninterrupted supply of tepid water.
Bradley plumbed emergency fixtures require a minimum of 30 psi flowing pressure in order to function as
designed and meet the ANSI/ISEA Z358.1 standard.
Self-closing spring-loaded valves are not UL classified to ANSI/ISEA Z358.1.
Before installation make sure that this equipment will meet the requirements of the potential hazardous
contaminants in your location.
Installation of this system must be completed by a qualified plumber in compliance with all national and
local codes. Compliance and conformity to drain requirements and other local codes and ordinances is the
responsibility of the installer.
Weekly Inspections
To ensure all emergency shower and eye/face wash fixtures are ready to be used when needed, regular checks
and maintenance must be conducted. Weekly inspections must be conducted on all safety equipment to make
sure a suitable flushing fluid supply is present and to make sure the equipment is in good operating condition.
Water Temperature
ANSI/ISEA Z358.1 requires tepid water. Suitable range is 60°F to 100°F (16°C to 38°C). Personal injury is
possible outside this temperature range.
Bradley • 215-1684 Rev. X: ECO 23-05-001A