3/400/50-60
• Check that the switch "SW1" is set to SOURCE.
WARNING: in cases where a single variable frequency drive is used to control two motors,
the thermal protection devices must be connected in series.
6.7.2.2 CONFIGURING THE DIFFERENTIAL PRESSURE TRANSMITTER
(TDP-S & TDP-D))
• If you wish to configure the equipment to operate under constant pressure control, you
can use differential pressure transmitter models TDP-S or TDP-D. If you wish to operate
with constant airflow control you must use the TDP-D model.
The way you connect the pressure tubes depends on the type of control required, as
shown in the diagram below:
3/400/50
3/230/400/50
56