Table 1
Tubing Size
Narrow (mm)
Wide (mm)
φ6.35(6.0)
φ9.52(9.0)
φ6.35(6.0)
φ12.7(12.0)
φ6.35(6.0)
φ15.88(5/8")
The above dimensions are for reference only,the actual product shall prevail.
• Fixing Installation Panel
Dismantle the metal installation board of the indoor unit. Adjust the installation board to horizontal position.The
⚫
height difference between the left and right sides of the installation board should less than 5mm.(Fig 4)
Drill holes and insert plastic expansion tubes at the appropriate locations on the wall and fix the installation
⚫
board on the wall with M5x30 screws. Ensure that there must be at least 4 fixed points in the wall. Ensure installation
board to horizontal position.
Drill holes as Fig. 5 shows. The hole, 80mm in diameter, should slightly slide down outwards..
⚫
Cut PVC tubes at a slight angle in the length shorter than wall thickness and inset it into the hole.(Fig.5)
⚫
⚫
Mount the wall cap.
Installation board
INSTALLATION MANUAL
Standard
Max tubing
tubing
Length (m)
Length (m)
3.5
3.5
4
Fig 4
Wall
Indoor
Wall cap
Fig 5
20
Height
Difference(m)
9
5
12
7
15
8
Installation board
Outdoor
PVC tube
Small angle
Additional
refrigerants
(g/.m)
15
15
15