Environmental correction
Power specifications indicated are with the following values:
Altitude:0m
Ambient temperature:25º
Factor "A"of environmental correction (Temperature and altitude):
Altitude
(meters)
25
0
1
500
0,93
1000
0,87
2000
0,75
3000
0,64
4000
0,54
Factor "B" of environmental correction (humidity):
Relative humidity 60 %
Relative humidity 80%
Relative humidity 90%
Relative humidity 100%
Example of power calculation according to atmospheric conditions.
3KW generator,
altitude: 1000m, Temperature: 35℃, Humidity: 80%
Power rating x (Factor A – factor B) = Actual Power
3
x (0.82
12. Warranty information
You machine has the following warranty:
2 years for machines billed to consumers (individuals).
1 year for machines billed to companies, partnerships, cooperatives,
autonomous parties...
The warranty covers any defect the machine may have during the warranty period, whenever the
machine's maintenance and care have been appropriate. The warranty will cover any parts needed
as well as labor.
The warranty does not cover consumables (filters, batteries, spark plugs) or preventive
maintenance operations. Normal wear and tear of the components is not covered either.
Ambient temperature (degrees Celsius)
30
35
0,98
0,96
0,91
0,89
0,85
0,82
0,73
0,71
0,62
0,6
0,52
0,5
correction factor C - 0.01
correction factor C - 0,02
correction factor C - 0,03
correction factor C - 0,04
-
0.02)
=
90
Relative humidity:30%
40
0,93
0,87
0,80
0,69
0,58
0,48
2.4KW
45
0,90
0,84
0,78
0,66
0,56
0,46