Descargar Imprimir esta página

Toshiba Carrier TCB-IFDMR01UP-UL Manual Del Usuario página 16

Ocultar thumbs Ver también para TCB-IFDMR01UP-UL:

Publicidad

Idiomas disponibles

Idiomas disponibles

TCB-IFDMR01UP-UL
(Terminal block with relay)
Shield wire MAX. 656'2" (200 m)
`
Al3
Input
0 - 10 V
Al3
Input
Name
AI3
Set temperature changed
AI4
Nothing
Analog Input 2 (DC 0 - 10 V)
TA type
10.00
Heating / Cooling
9.70
8.95
8.20
7.45
6.70
5.95
5.20
4.45
3.70
2.95
2.20
1.45
0.70
0.00
Locally procured
0 - 10 V Signal (+)
GND (-)
• To use this control, set DN [4A9] = 1.
• For TA and TF type, the set temperature can be changed
according to the 0 - 10 V input of AI3.
• In the set temperature with the remote controller and this
control, the post-setting is prioritized.
• The set temperature can be changed only for cooling and
heating operations.
Cannot be used.
Set temp
(V)
84°F / 84°F
9.50
82°F / 82°F
8.75
81°F / 81°F
8.00
79°F / 79°F
7.25
77°F / 77°F
6.50
75°F / 75°F
5.75
73°F / 73°F
5.00
72°F / 72°F
4.25
70°F / 70°F
3.50
68°F / 68°F
2.75
66°F / 66°F
2.00
65°F / 65°F
1.25
65°F / 65°F
0.50
Description
TF type
10.00
9.70
8.95
8.20
7.45
6.70
5.95
5.20
4.45
3.70
2.95
2.20
1.45
0.70
0.00
– 14 –
✓ : Available ✕ : Prohibition
TA
-
Set temp
(V)
Heating / Cooling
86°F / 77°F
9.50
84°F / 75°F
8.75
82°F / 73°F
8.00
81°F / 72°F
7.25
79°F / 70°F
6.50
77°F / 68°F
5.75
74°F / 66°F
5.00
73°F / 65°F
4.25
72°F / 63°F
3.50
70°F / 61°F
2.75
68°F / 59°F
2.00
66°F / 57°F
1.25
65°F / 55°F
0.50
DDC
TF
-
-

Publicidad

loading

Este manual también es adecuado para: