Descargar Imprimir esta página

RHOSS Compact-Y SM TCAEY 122 P0 Instrucciones De Uso página 31

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

II.4.3
STORAGE CONDITIONS
The units cannot be stacked. The temperature limits for storage are
-20÷50°C.
II.5
INSTRUCTIONS FOR INSTALLATION
DANGER!
Installation must only be carried out by skilled
technicians, qualified to work on air conditioning
and cooling systems. Incorrect installation could
cause the unit to run badly, with a consequent
noticeable deterioration in performance.
DANGER!
The unit must be installed according to national or
local rules in force at the time of installation. The
documentation for accessories supplied loose
included with each kit.
DANGER!
The machine is designed for outdoor installation.
Segregate the unit if installed in areas accessible to
persons under 14 years of age.
DANGER!
Some internal parts of the unit may cause cuts. Use
suitable personal protection gear.
DANGER!
When the outdoor temperature is around zero, the
water normally produced during the defrosting of
the coils could form ice and make the flooring near
the installation area slippery.
If the unit is not fixed to anti-vibration supports (KSA), once it has been
set on the ground, it must be solidly bolted down to the floor using M6
metric threaded bolts. Slots are provided in the base for this purpose.
II.5.1
INSTALLATION SITE REQUIREMENTS
The installation site should be chosen in accordance with that set out in
the EN 378-1 standard and in keeping with the requirements of the EN
378-3 standard. When selecting the installation site, risks posed by
accidental refrigerant leakage from the unit should also be taken into
consideration.
II.5.1.1
Outdoor installation
Machines designed for outdoor installation must be positioned so as to
avoid any refrigerant gas leakage entering the building and posing a
hazard to people's health.
If the unit is installed on terraces or building roofs, adequate safety
measures must be taken in order to ensure that any gas leaks cannot
enter the building through ventilation systems, doors or similar
openings.
In the event that the unit is installed inside a walled-in structure (usually
for aesthetic reasons), these structures must be suitably ventilated in
order to prevent the formation of dangerous concentrations of
refrigerant gas.
II.5.2
CLEARANCE SPACES, POSITIONING
IMPORTANT!
Before installing the unit, check the noise limits
permissible in the place in which it will be used.
IMPORTANT!
The unit should be positioned to comply with the
minimum recommended clearances, bearing in
mind the access to water and electrical
connections.
The unit is designed for outdoor installation. The unit should be installed
to comply with the minimum recommended clearances, bearing in mind
the access to water and electrical connections. The unit should be
correctly levelled and positioned on a supporting surface capable of
sustaining its full weight. It must not be installed on brackets or shelves.
L4
Model
L1
mm
L2
mm
L3
mm
L4
mm
31
Compact-Y SM
L1
L2
L3
122
127
130
300
400
400
600
600
600
with open outlet
300
300
300

Publicidad

loading