MODEL 8145 FRESH AIR VENTILATOR
VENTILATION CONTROLLER
FILTER
COVER
SURFACE MOUNT
BRACKET LOCATION
SAFETY INSTRUCTIONS
1. 120 Volts may cause serious injury from electric shock. Disconnect electrical power before starting installation or servicing. Leave power
disconnected until installation/service is completed.
2. Sharp edges may cause serious injury from cuts. Use care when cutting plenum openings and handling duct work.
1. Read all instructions before beginning installation.
2. Improper installation may cause property damage or injury. Installation, service, and maintenance must be performed by a qualified service
technician.
TABLE OF CONTENTS
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Introduction and Compliance Statement . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Install Electrical Outlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Ventilator Location and Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Mount the Ventilator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Mount Intake Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Install Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Model 8145NC – Wiring to Various Controls . . . . . . . . . . . . . . . . . . . . . . . . .5
Model 8145NC – Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Model 8145NC – Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
10014353 B2208589A 4.20
Model 8145 and 8145NC
Fresh Air Ventilator
Installation and Operating Instructions
HIGH PRESSURE
PORT
WARNING
CAUTION
READ AND SAVE THESE INSTRUCTIONS
MODEL 8145NC FRESH AIR VENTILATOR
LOW PRESSURE
PORT
INLET COLLAR AND
NORMALLY CLOSED
POWER DAMPER
Model 8145 – Wiring the Control to the HVAC System . . . . . . . . . . . . . . .6
Model 8145 – Connecting the Control to the Ventilator . . . . . . . . . . . . . . . 7
Model 8145 – Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Model 8145 – Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Measure Delivered Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Model 8145 – Set Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Model 8145 – Rater/Inspector Verification . . . . . . . . . . . . . . . . . . . . . . . . . 10
Model 8145 – Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Filter Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1
Internal Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
VENTILATION TERMINALS
JOIST MOUNT
OUTLET
BRACKET LOCATION
COLLAR
English 1

Publicidad

loading

Resumen de contenidos para Aprilaire 8145

  • Página 1 Model 8145 – Wiring the Control to the HVAC System . . . . . . . . . . . . . . .6...
  • Página 2 INTRODUCTION AND COMPLIANCE STATEMENT The Model 8145 and 8145NC Fresh Air Ventilators are designed to bring in precisely the right amount of outdoor air into today’s efficiently designed homes . Duct the inlet of the ventilator to an outdoor air intake and duct the discharge to the HVAC system, then simply plug the unit in, set the amount of needed ventilation and select the desired temperature limits .
  • Página 3 VENTILATOR LOCATION AND ORIENTATION If the outlet of the ventilator is not ducted, or if small sections of collapsible duct (i . e . flex duct) are attached to the outlet, then the FIGURE 2 – CLEARANCES FOR SERVICING ventilator must be mounted to minimize the possibility of accessing moving parts (see Cautions below) .
  • Página 4 MOUNT INTAKE HOOD Install a weather tight hood with a bird screen . Cut a hole in the exterior wall that is large enough to fit 6" insulated flexible duct through with minimal compression of the insulation . Pull the duct through the hole and attach the flex duct to the collar of the hood .
  • Página 5 MODEL 8145NC – WIRING TO VARIOUS CONTROLS Suggested Controls: • Aprilaire IAQ Control Models 8910, 8910W or 8920W • Aprilaire Thermostat Models 8620 or 8620W • Aprilaire Model 8120X Digital Ventilation Controller Select the diagram that corresponds to the control to be used . Wire the controls to the HVAC equipment and any other IAQ accessory in accordance with the literature provided with the control .
  • Página 6 MODEL 8145NC – SEQUENCE OF OPERATION Refer to the installation manual provided with the control that is wired to the Model 8145NC . MODEL 8145 – WIRING THE CONTROL TO THE HVAC SYSTEM NOTICE FIGURE 9 – REMOVE CONTROL FROM MOUNTING PLATE...
  • Página 7 O = REV. VALVE, COOLING GS = FAN INPUT GH = FAN OUTPUT MODEL 8145 – CONNECTING THE CONTROL TO THE VENTILATOR Plug the Control Connector into the back of the control at the location shown in FIGURE 12 . Route FIGURE 12 –...
  • Página 8 60 minutes/hour or you can 90-2520 simply place a jumper between the VENT terminals of the ventilator . Model 8145 – Turn on the ventilator by using the “Up” button to increase the ventilation setting TABLE 3 – DELIVERED AIRFLOW CORRESPONDING TO MEASURED PRESSURE to 60 MIN .
  • Página 9 . IMPORTANT NOTE: The 8145 control senses the temperature and humidity of the outdoor air. To prevent extended periods of inactivity, set the control mode to codE, or if setting to cFrt (comfort), set the RH limits to OFF.
  • Página 10 (Floor Area ft .01) + (No. of Bedrooms + 1) MODEL 8145 – SEQUENCE OF OPERATION “CODE” SETTING The control will turn on ventilation with a heating, cooling or fan call for the set number of minutes during a one-hour cycle period . If the outdoor temperature is above the high temperature ventilation limit, ventilation will not occur with a cool or fan call, but if it is below the low temperature ventilation limit it will occur with a heat call .
  • Página 11 . 90-2514 INTERNAL SCHEMATICS FIGURE 15 – MODEL 8145 INTERNAL SCHEMATIC CAPPED RED & WHITE WIRES ARE LOCATED INSIDE THE FILTER DOOR TO POWER THE CONTROL (R & C TERMINALS) FROM THE POWER PCB ASSEMBLY. USE ONLY IF THE VENTILATON CONTROLLER WILL NOT BE WIRED TO THE HVAC SYSTEM.
  • Página 12 WARRANTY REGISTRATION Visit us online at www.aprilaire.com to register your Aprilaire product . If you do not have online access, please mail a postcard with your name, address, phone number, email address, product purchased, model number, date of purchase, and dealer name and address to: Research Products Corporation, P . O . Box 1467, Madison, WI 53701 .
  • Página 13 Modelo 8145: cableado del control al sistema de HVAC . . . . . . . . . . . . . . . .
  • Página 14 INTRODUCCIÓN Y DECLARACIÓN DE CUMPLIMIENTO El ventilador de aire fresco modelo 8145 y 8145NC está diseñado para incorporar de manera precisa la cantidad correcta de aire del exterior a las viviendas actuales diseñadas eficientemente . Conduzca la entrada del ventilador a una entrada de aire exterior y conduzca la descarga al sistema de HVAC; luego, simplemente enchufe la unidad, configure la cantidad de ventilación necesaria y seleccione los límites de temperatura deseados .
  • Página 15 UBICACIÓN Y ORIENTACIÓN DEL VENTILADOR Si la salida del ventilador no tiene conductos o si pequeñas secciones del conducto plegable (es decir, conducto flexible) están conectadas a la salida, FIGURA 2: ESPACIOS PARA REALIZAR EL MANTENIMIENTO el ventilador debe instalarse de manera tal que se minimice la posibilidad de acceder a piezas móviles (consulte las PRECAUCIONES a continuación) .
  • Página 16 INSTALACIÓN DEL EXTRACTOR DE ADMISIÓN Instale un extractor hermético con una malla contra pájaros . Haga un agujero en la pared exterior que sea lo suficientemente grande como para que ingrese un conducto flexible aislado de 6 in con una compresión mínima del aislamiento .
  • Página 17 MODELO 8145NC: CABLEADO PARA VARIOS CONTROLES Controles sugeridos: • Los modelos con control de Calidad del aire interior (Indoor Air Quality, IAQ) 8910, 8910W o 8920W de Aprilaire • Los modelos de termostato 8620 o 8620W de Aprilaire • Controlador digital del sistema de ventilación modelo 8120X de Aprilaire Seleccione el diagrama que corresponda de acuerdo con el sistema de control que se utilizará...
  • Página 18 MODELO 8145NC: SECUENCIA DE FUNCIONAMIENTO Consulte el manual de instalación que se proporciona con el sistema de control que está conectado al modelo 8145NC . MODELO 8145: CABLEADO DEL CONTROL AL SISTEMA DE HVAC AVISO FIGURA 9: RETIRO DEL SISTEMA DE CONTROL DE LA PLACA DE MONTAJE...
  • Página 19 GS = ENTRADA DEL VENTILADOR GH = SALIDA DEL VENTILADOR MODELO 8145: CÓMO CONECTAR EL SISTEMA DE CONTROL AL VENTILADOR Enchufe el conector del sistema de control en la parte posterior del control en la ubicación que se muestra en FIGURA 12: CONEXIÓN DEL SISTEMA DE CONTROL AL VENTILADOR...
  • Página 20 1. Asegúrese de que el ventilador esté enchufado y conectado a un sistema de control externo (modelo 8145NC) o que el sistema de control integral esté conectado al sistema de HVAC (modelo 8145) . 2. Utilice conductos flexibles de 1/4 in para conectar un indicador de presión configurado para medir pulgadas de columna de agua (a veces se muestra como “in .
  • Página 21 . NOTA IMPORTANTE: el sistema de control del modelo 8145 detecta la temperatura y la humedad del aire exterior. Para evitar que se produzcan períodos prolongados de inactividad, establezca el modo del sistema de control en codE (Código), o si la configuración está establecida en cFrt (Comodidad), establezca los límites de RH en OFF (Apagado).
  • Página 22 MODELO 8145: VERIFICACIÓN DEL EVALUADOR/INSPECTOR Para verificar la configuración del tiempo de ventilación, presione el botón Select (Seleccionar) para desplazarse por las opciones de Required Continuous CFM (CFM constantes necesarios) y Measured CFM (CFM medidos) calculados para esta instalación . Si algún valor no coincide con el valor esperado, se debe ingresar al menú de configuración para modificar la superficie cubierta, la cantidad de habitaciones o los CFM medidos .
  • Página 23 90-2514 ESQUEMAS INTERNOS FIGURA 15: ESQUEMA INTERNO DEL MODELO 8145 LOS CABLES RECUBIERTOS DE COLOR ROJO Y BLANCO SE ENCUENTRAN DENTRO DE LA PUERTA DEL FILTRO Y SE UTILIZAN PARA ALIMENTAR EL SISTEMA DE CONTROL (TERMINALES R Y C) A PARTIR DEL TABLERO DE CIRCUITO IMPRESO DE CONTROL DE POTENCIA.
  • Página 24 GARANTÍA LIMITADA El ventilador de aire fresco de Research Products Corporation de Aprilaire® cuenta con una garantía de cinco (5) años a partir de la fecha de instalación que cubre defectos materiales o de mano de obra . La obligación exclusiva de Research Products Corporation bajo esta garantía es la de suministrar, sin cargo, un repuesto para cualquier pieza que esté dañada dentro del período de los cinco (5) años mencionado y usted o su proveedor original puede devolverlo hasta treinta (30) días después del período de 5 (cinco) años a Research Products Corporation, Madison, Wisconsin 53701, junto con el número de modelo y la fecha de...