09: Programmable outlets setting
⚫
Interface
10 : Autonomy limitation setting
⚫
Interface
11 : Total battery capacity (Ah)
⚫
Interface
12 : Maximum charger current setting
⚫
Interface
13 : Charger boost voltage setting
⚫
Interface
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com Hot Line Tel : +33
(0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 11 23 AA 59 204 16
Configuration
Parameter 2: Set backup time limits for programmable outlets.
0-999: set backup time limits in minutes from 0 to 999 for
programmable outlets connected to non-critical devices in battery
mode. (Default: 999)
Configuration
Parameter 2: Set backup time in battery mode for general
outlets.
0-999: set backup time in minutes from 0 to 999 for general use
in battery mode.
0: When set to "0", the backup time will be only 10 seconds.
999: When set to "999", the backup time setting will be disabled.
(Default)
Configuration
Parameter 2: Set the total UPS battery capacity (unit: Ah).
7-999: set total battery capacity from 7 to 999. Please set this
value if an external battery pack is connected.
If the UPS is a standard model, the default value is 9 Ah.
If the UPS is an extended-range model, the default value is 65 Ah.
Configuration
Parameter 2: Set maximum charging current. This setting is only
available for the extended-range model.
1/2/4/6/8: set maximum charging current to 1/2/4/6/8 amps.
(Default: 8A)
For the standard model, the default charging current is 1.5 A.
Configuration
Parameter 2: Set charger boost voltage.
2.25-2.40: set charger boost voltage from 2.25 V/cell to 2.40 V/cell
(default: 2.36 V/cell).
45