RECEPTACLES
[
cAuTioN
. NEVER attempt to power a device requiring
more amperage
than generator
or receptacle
can supply.
. DO NOT overload the generator. See "Don't
Overload
Generator".
1
1201240 Volt AC, 30 Amp,
Locking
Receptacle
Use a NEMA L14-30 plug with this receptacle.
Connect
a
4-wire
cord set rated for 250Volt
AC loads at 30Amps
(or
greater) (Figure 5).You can use the same 4-wire
cord if you
_[an to run a 120Volt load.
4=Wire Cord Set
j--
--"_
Y (Hot)
(Neutral)
/_
X (Hot)
Ground (Green)
NEMA
LI4=30
This receptacle
powers
I20/240VoItAC,
60 Hz, single
phase loads requiring
up to 5,600 watts
of power
(5.6 kW)
at 23.3 Amps for 240Volts
or two independent
120Volt
loads at 20 Amps each.The
outlet
is protected
by
push-to-reset
circuit breakers.
I 2.0Volt AC, 2.0 Amp,
Duplex
Receptacles
Each duplex receptacle (Figure 6) is protected
against
overload by a push-to-reset
circuit breaker.
@
Use each receptacle
to operate
120Volt AC, single-phase,
60 Hz electrical
loads requiring
up to 2,400 watts
(2.4 kW)
at 20 Amps of current.
Use cord sets that are rated for
125 Volt AC loads at 20 Amps (or greater).