Descargar Imprimir esta página

Ferroli ATLAS D ECO 30 K 100 UNIT Instrucciones De Uso, Instalación Y Mantenimiento página 45

Ocultar thumbs Ver también para ATLAS D ECO 30 K 100 UNIT:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 21
ATLAS D ECO 30/42 K 100/130 UNIT
3.5 Electrical connections
Connection to the electrical grid
The unit's electrical safety is only guaranteed when cor-
B
rectly connected to an efficient earthing system executed
according to current safety standards. Have the efficiency
and suitability of the earthing system checked by profes-
sionally qualified personnel. The manufacturer is not re-
sponsible for any damage caused by failure to earth the
system. Also make sure that the electrical system is ade-
quate for the maximum power absorbed by the unit, as
specified on the boiler dataplate.
The boiler is prewired and provided with a Y-cable and plug for connection to the elec-
tricity line. The connections to the grid must be made with a permanent connection and
equipped with a bipolar switch whose contacts have a minimum opening of at least 3
mm, interposing fuses of max. 3A between the boiler and the line. It is important to re-
spect the polarities (LINE: brown wire / NEUTRAL: blue wire / EARTH: yellow-green
wire) in making connections to the electrical line. During installation or when changing
the power cable, the earth wire must be left 2 cm longer than the others.
The user must never change the unit's power cable. If the
B
cable gets damaged, switch off the unit and have it
changed solely by professionally qualified personnel. If
changing the electric power cable, use solely "HAR H05
VV-F" 3x0.75 mm2 cable with a maximum outside diam-
eter of 8 mm.
Room thermostat (optional)
IMPORTANT: THE ROOM THERMOSTAT MUST HAVE
B
VOLTAGE-FREE CONTACTS. CONNECTING 230 V TO
THE ROOM THERMOSTAT TERMINALS WILL PERMA-
NENTLY DAMAGE THE ELECTRONIC BOARD.
When connecting time controls or a timer, do not take the
power supply for these devices from their breaking con-
tacts Their power supply must be by means of direct con-
nection from the mains or with batteries, depending on the
kind of device.
Accessing the electrical terminal block
Undo the two screws "A" located on the top part of the control panel and remove the
cover.
fig. 29 - Accessing the terminal board
3.6 Connection to the flue
The unit must be connected to a flue designed and built in compliance with the current
regulations. The pipe between the boiler and flue must be made from material suitable
for the purpose, i.e. heat and corrosion resistant. Ensure the seal at the joints.
A
A
cod. 3541Q564 - Rev. 01 - 11/2022
4. SERVICE AND MAINTENANCE
All adjustment, conversion, commissioning and maintenance operations described be-
low must only be carried out by Qualified Personnel (meeting the professional technical
requirements of current regulations) such as the personnel of the Local After-Sales
Technical Service.
FERROLI declines any liability for damage and/or injury caused by unqualified and un-
authorised persons tampering with the unit.
4.1 Adjustments
TEST mode activation
Press the heating buttons (details 3 and 4 - fig. 1) together for 5 seconds to activate the
TEST mode. The boiler switches on irrespective of the system or DHW request.
The heating symbol (detail 24 - fig. 1) and DHW symbol (detail 12 - fig. 1) flash on the
display.
fig. 30 - TEST mode
To deactivate the Test mode, repeat the activation sequence.
The TEST mode is automatically disabled in any case after 15 minutes.
Burner adjustment
The burner is factory-set as given in table 2. The burner can be set to a different output
by acting on the pump pressure, nozzle, head adjustment, and air adjustment as per the
following paragraphs. In any case, the new adjusted output must fall within the boiler's
nominal operating range. After making any adjustments, using a combustion analyser
check that the CO
content in the fumes is between 11% and 12%.
2
Nozzle flow rate table for oil
table 2 gives the oil flow rates (in kg/h) according to the change in pump pressure and
nozzles.
N.B. - The values given below are only approximate, since nozzle flow rates can vary by
± 5%. Also, with burners having a preheater, the fuel flow rate decreases by about 10%.
Table. 2
NOZZLE
8
9
G.P.H.
1,32
1,40
0.40
15,66
16,60
1,57
1,65
0.50
18,62
19,57
1,93
2,01
0.60
22,89
23,83
2,12
2,25
0.65
25,14
26,68
2,50
2,65
0.75
29,65
31,43
2,92
3,10
0.85
34,63
36,76
3,30
3,50
1.00
39,13
41,51
4,12
4,40
1.25
48,86
52,18
4,95
5,30
1.50
58,70
62,85
5,69
6,18
1.75
67,48
73,29
Flow rate at nozzle outlet in kg/h
eco
bar
Pump pressure (bar)
10
11
12
13
1,47
1,54
1,61
1,68
17,43
18,26
19,09
19,92
1,73
1,81
1,89
1,97
20,51
21,50
22,42
23,36
2,23
2,32
2,42
2,52
26,44
27,51
28,70
29,88
2,40
2,63
2,74
2,80
28,46
31,19
32,49
33,21
2,80
2,95
3,07
3,20
33,21
34,99
36,41
37,95
3,27
3,45
3,60
3,75
38,78
40,92
42,69
44,47
3,67
3,85
4,02
4,20
43,52
45,66
47,67
48,72
4,61
4,82
5,03
5,25
54,67
57,16
59,65
62,26
5,55
5,80
6,05
6,30
65,82
68,78
71,75
74,72
6,46
6,75
7,06
7,38
76,61
80,05
83,73
87,53
EN
14
1,75
20,75
2,05
24,31
2,64
31,31
2,91
34,51
3,33
39,49
3,90
46,25
4,38
51,95
5,46
64,75
6,55
77,68
7,96
91,20
45

Publicidad

loading

Este manual también es adecuado para:

Atlas d eco 42 k 130 unit