Parameter Table; Base Menu - ITALFARAD PFC144evo Manual De Uso

Regulador automático de factor de potencia
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Below are listed all the programming parameters in tabular form. For each parameter are indicated the possible
setting range and factory default, as well as a brief explanation of the function of the parameter. The description of
the parameter shown on the display can in some cases be different from what is reported in the table because of
the reduced number of characters available. The parameter code can be used however as a reference.
Note: the parameters shown in the table with a shaded background are essential to the operation of the system,
thus they represent the minimum programming required for operation.
COD
DESCRIPTION
P.01
CT primary
P.02
CT secondary
P.03
CT read phase
P.04
CT wiring polarity
P.05
Voltage read phase
P.06
Smallest step power
Rated installation
P.07
voltage
P.08
Nominal frequency
P.09
Reconnection time
P.10
Sensitivity
P.11
Step 1 function
P.12
Step 2 function
P.13
Step 3 function
P.14
Step 4 function
P.15
Step 5 function
P.16
Step 6 function
P.17
Step 7 function
P.19
Cos-phi setpoint
Alarm messages
P.20
language
Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: italfarad@italfarad.com Web: www.italfarad.com

Parameter table

Base menu

ACC UoM
DEF
Usr
A
OFF
Usr
A
5
Usr
L1
Usr
Aut
Usr
L2-L3
Usr
Kvar
1.00
Usr
V
400V
Usr
Hz
Aut
Adv
sec
60
Usr
sec
60
Usr
OFF
Usr
OFF
Usr
OFF
Usr
OFF
Usr
OFF
Usr
OFF
Usr
OFF
0.95
Usr
IND
Usr
ENG
ITALFARAD S.p.A. via IV novembre n.1 Minerbio Bo Italy
RANGE
OFF / 1...10.000
1 / 5
L1 - L2– L3
Aut - Dir - Inv
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N
0.10 ... 10000
50 ... 50000
Aut - 50Hz - 60Hz - Var
1 ... 30000
1 ... 1000
OFF - 1...32 - ON - NOA - NCA - FAN - MAN - AUT - A01...A12
=
=
=
=
=
=
0.50 Ind – 0.50 Cap
ENG - ITA - FRA - SPA - POR - DEU
E
N
47

Publicidad

Tabla de contenido
loading

Tabla de contenido