Select the position ρ (4 pole) in the FUNCTION Selector Switch
2.
and connect the rods, as it is shown in figure 02.
3.
Find
the
most
Pushbutton.
4.
To obtain the soil resistivity value, Wenner's equation should be
applied. In its simplified form, this equation is as follows:
Where:
ρ = soil resistivity value, expressed in [Ωm]
•
π = 3.14159
•
R = value shown on the display.
•
D = distance between the rods, expressed in meters.
•
appropriate
range
ρ = 2πRD
12
and
press
the
START