Installation
The internal power supply of a central unit can only generate limited
electrical power via the system bus. The power requirements of all
installed slaves can be determined as a busload as follows: The
maxim system bus length is derived from the voltage drop across the
cables used.
Slave
Transmitter with electrochemical Dräger sensor
Relay module
Converter module
for each 4 ... 20 mA loop connected which is supplied by the
VarioGard system bus
(i.e. maximum of 2 + 4 x 1.5 = 8 busloads)
The total of all the busloads must not exceed 32 without an additional
power supply. The maximum total cable lengths, depending on the
total planned busloads, are shown below:
Cross-section
4
8
JE-Y(St)Y
1000 m 690 m 460 m
2 x 2 x 0.8 mm
2
(0.5 mm
)
H05VV-R 3 X
1300 m 1300 m 1300 m 1000 m 800 m 600 m 550 m 500 m
1.5 (NYM-O)
2
(1.5 mm
)
36
Busloads
1
4
2
1,5
Number of busloads
12
16
20
24
28
340 m 270 m 230 m 190 m 170 m
VarioGard
L1
L2
The maximum length of the system bus cable is determined by the
total length of the slave cables
(e. g. L1 + L2 + L3 + L4 + L5).
Use cables with a cross-section of between 0.5 mm
e. g. NYM-O 3 x 1.5 mm
2 x 0.8 mm (0.5 mm
32
L3
L4
L5
2
2
, NYM-J 4 x 1.5 mm
or JE-Y(St)Y 2 x
2
).
Dräger VarioGard
2
2
and 1.5 mm
,