Use only a 3-conductor or a 4-conductor UL-listed range cord. These cords may be
provided with ring terminals on wire and a strain relief device.
A range cord rated at 40 amps with 125/250 minimum volt range is required.
A 50 amp range cord is not recommended but if used, it should be marked for
use with nominal 1⅜" diameter connection openings. Care should be taken to
center the cable and strain relief within the knockout hole to keep the edge from
damaging the cable.
•
Because range terminals are not accessible after range is in position, flexible
service conduit or cord must be used.
NOTE
•
If conduit is being used, go to Step 5 on pages 19 ~ 20.
•
If the power connection is plugged in improperly, the following message
appears on the display.
•
LCD, PMOLED : Wire installation fail
LED : bAd LinE
•
•
Reconnect the power connection properly, and the message disappears.
ALL NEW BRANCH-CIRCUIT CONSTRUCTIONS, MOBILE HOMES,
RECREATIONAL VEHICLES AND INSTALLATIONS WHERE LOCAL
CODES DO NOT ALLOW GROUNDING THROUGH NEUTRAL, REQUIRE A
4-CONDUCTOR UL-LISTED RANGE CORD.
Install_NY63T8751S_DG68-01242A-00_EN+MES+CFR.indb 17
Step 3. Accessing the power cord connection
Remove the rear access cover and loosen the screw with a screwdriver. The
terminal block will then be accessible.
Terminal block
Access cover
Specified power-supply-cord kit rating
Range rating, watts
Specified rating
of power-supply-
120/240
120/208
cord kit, amperes
volts 3-wire
volts 3-wire
8750 - 16500 7801 - 12500
40 or 50A
Diameter (inches) of range
connection opening
Power cord
Conduit
1⅜"
1⅛"
English 17