5
Change the settings with the
•
Temp. range: No (unrestricted) or Yes (restricted)
•
Cool•Drying: Upper and lower limit temperature
(1ºC/1ºF increments)
•
Heat: Upper and lower limit temperature (1ºC/1ºF increments)
•
Auto: Upper and lower limit temperature (1ºC/1ºF increments)
Temperature setting ranges
Mode
Lower limit
*1
Cool•Drying
*3
(67 ~ 87ºF)
*2
Heat
*3
(63 ~ 83ºF)
Auto
*4
(67 ~ 83ºF)
* The settable range varies depending on the connected unit.
*1 Temperature ranges for the Cool, Drying, and Auto (dual set
point) modes can be set.
*2 Temperature ranges for the Heat and Auto (dual set point)
modes can be set.
*3 Temperature ranges for the Heat, Cool, and Drying modes must
meet the conditions below:
• Upper limit for cooling - upper limit for heating ≥ Minimum
temperature difference (varies with indoor unit model)
• Lower limit for cooling - lower limit for heating ≥ Minimum
temperature difference (varies with indoor unit model)
*4 Temperature range for the Auto (single set point) mode can be
set.
Press the
SELECT/HOLD
A confirmation screen will appear.
Navigating through the screens
• To go back to the Main menu ..........
• To return to the previous screen ......
will appear on the Status display and the Main
display in the Full mode when the temperature range
is restricted.
or
button.
F3
F4
Upper limit
19 ~ 30ºC
30 ~ 19ºC
(87 ~ 67ºF)
17 ~ 28ºC
28 ~ 17ºC
(83 ~ 63ºF)
19 ~ 28ºC
28 ~ 19ºC
(83 ~ 67ºF)
button to save the settings.
button
MENU
button
RETURN
47