Electrical connections
Be sure your appliance is properly installed and grounded by a qualified technician. Ask your dealer to recommend a qualified
technician or an authorized repair service.
This appliance is manufactured with a green GROUND wire connected to the oven chassis. After making sure that the power has
been turned off, connect the flexible conduit from the oven to the junction box using a U.L. listed conduit connector. Figures A and
B and the instructions provided below present the most common way of connecting the ovens.
Your local codes and ordinances, of course, take precedence over these instructions. Complete electrical connections according to
local codes and ordinances.
"WARNING" Risk of Electric Shock, frame grounded to neutral of appliance through a link.
Grounding through the neutral conductor is prohibited for new branch-circuit installations (1996 NEC); mobile homes; and
recreational vehicles, or in an area where local codes prohibit grounding through the neutral conductor. For installations where
grounding through the neutral conductor is prohibited:
• Disconnect the ground from the neutral at free end of conduit;
• Use grounding terminal or lead to ground unit; and
• Connect neutral terminal or lead to branch circuit neutral in usual manner.
3-Wire branch circuit (for US only)
Refer to Figure A, where local codes allow the connection of
GROUND wire from the oven to the branch circuit NEUTRAL
wire (gray or white colored wire):
• If local codes permit, connect the green GROUND wire
from the oven and the white wire from the oven to the
branch circuit NEUTRAL wire (gray or white colored wire).
• Connect the red and black leads from the oven to the
corresponding leads in the junction box.
GROUNDED NEUTRAL
A
Junction box
power supply
Red wires
White wires
Bare or
green wire
Cable
from oven
Cable from
Black wires
UL listed conduit
connector
Installation Instructions
4-Wire branch circuit (for US and Canada)
Refer to Figure B:
• Disconnect ground from neutral at free end of conduit.
• Connect the green GROUND wire from the oven to the
GROUND wire in the junction box (bare or green colored
wire).
• Connect the red and black leads from the oven to the
corresponding leads in the junction box.
• Connect the white wire from the oven to the NEUTRAL (gray
or white) wire in the junction box.
UNGROUNDED NEUTRAL
B
Junction box
Cable from
power supply
Red wires
Bare or
green wire
Cable
from oven
EN
White wires
Black wires
UL listed conduit
connector
9