3
2
1
Figure 6: OI Menu
MENU SCREEN
1.Line Selection Panel
2.Zone Selection Panel
3.System Menu
4.Historical Data Viewer
5.Current Zone Information/Parameters
6.Edit Parameters
7.Locate Zone
8.System Overview
SCHERMATA MENU
1.Pannello di selezione della linea
2.Pannello di selezione della zona
3.Menu di sistema
4.Visualizzatore di dati storici
5.Informazioni sulla zona corrente/Parametri
6.Modifica i parametri della zona selezionata
PANTALLA DE MENÚ
1.Panel de selección de línea
2.Panel de selección de zona
3.Menú del sistema
4.Visor de datos históricos
5.Información/parámetros de la zona actual
6.Editar los parámetros de la zona seleccionada
菜单屏幕
1.行选择面板
2.区域选择面板
3.系统菜单
4.历史数据查看器
5.当前区域信息/参数
6.编辑选择区域参数
®
© BriskHeat
Corporation. All rights reserved.
®
LYNX
System Instructions
4
5
6
7
8
MENÜ-ANZEIGE
1.
Linienwahlanzeige
2.
Zonenwahlanzeige
3.
Systemmenü
4.
Anzeige historischer Daten
5.
Aktuelle Zoneninformationen/Parameter
SCHERMATA MENU
1.
Volet de sélection de ligne
2.
Volet de sélection de zone
3.
Menu Système
4.
Visionneuse de données historiques
5.
Paramètres/informations sur la zone actuelle
メニュー画面
1.
ライン選択パネル
2.
ゾーン選択パネル
3.
システムメニュー
4.
履歴データビューア
5.
現在のゾーン情報/パラメーター
6.
選択したゾーンパラメーターの編集
7.
機能の特定 (点滅光の作動)
8.
システム構成
17
TROUBLESHOOTING GUIDE
Please read this guide prior to contacting BriskHeat with any issues with your system. This
guide is designed to answer the most commonly asked troubleshooting questions. If the
below corrective actions do not work, you are unable to identify the problem, or otherwise
need additional assistance, please contact BriskHeat at: 1-800-848-7673 (U.S. / Canada),
1-614-294-3376 (worldwide), or bhtsales1@briskheat.com.
Issue
Suggested Corrective Action
Module does not turn on
Verify Module is properly attached to the Dock
and that both Module clips have been fully seated.
Verify that power is connected to the Dock, and
that all Docks in a String are properly connected.
Verify that the supply power is turned on and that
the supply power fuses and breakers are intact.
Module LED is purple and Module
Change Module control mode from "Disabled" to
does not heat
another mode.
Module displays "FFF"
Verify Module is properly attached to the Dock
and that both Module clips have been fully seated.
Verify that the correct sensor type is properly
connected if using a Stand-alone Dock.
Module displays "ddd"
Verify Module is properly attached to the Dock
and that both Module clips have been fully seated.
Module displays high temp with red
Verify Module is properly attached to the Dock
LED on initial startup
and that both Module clips have been fully seated.
Module LED is blinking white
Disable Locate Mode from the OI.
Module LED is blinking red but dis-
The Module exceeded the High Alarm setpoint
plays
during operation. Manually unlatch the High Alarm
temperature below the High Alarm
to clear the blinking.
setpoint
Module LED is solid red
Ensure that the ambient temperature has not
exceeded the listed temperature ratings.
Verify Module is properly attached to the Dock
and that both Module clips have been fully seated.
Cannot remove Module from Dock
Firmly depress top edge of both Module clips
simultaneously, pull Module straight away from
Dock. Pry bottom of Module clips to assist with
disengagement if required.
®
© BriskHeat
Corporation. All rights reserved.
®
LYNX
System Instructions
18